8.2.3.3
Power supply quality
M13852-16 v1
The setting has to be well above the highest occurring "normal" voltage and below the highest
acceptable voltage, due to regulation, good practice or other agreements.
8.2.3.4
High impedance earthed systems
M13852-19 v6
In high impedance earthed systems, earth-faults cause a voltage increase in the non-faulty
phases. Two step overvoltage protection (OV2PTOV) is used to detect such faults. The setting
must be above the highest occurring "normal" voltage and below the lowest occurring voltage
during faults. A metallic single-phase earth-fault causes the non-faulted phase voltages to
increase a factor of √3.
8.2.3.5
The following settings can be done for the two step overvoltage
protection
M13852-22 v10
ConnType: Sets whether the measurement shall be phase-to-earth fundamental value, phase-
to-phase fundamental value, phase-to-earth RMS value or phase-to-phase RMS value.
Operation: Off/On.
UBase (given in GlobalBaseSel): Base voltage phase to phase in primary kV. This voltage is used
as reference for voltage setting. OV2PTOV measures selectively phase-to-earth voltages, or
phase-to-phase voltage chosen by the setting
ConnType. The function will operate if the
voltage gets lower than the set percentage of
UBase. When ConnType is set to PhN DFT or PhN
RMS then the IED automatically divides set value for UBase by √3. When ConnType is set to
PhPh DFT or PhPh RMS then set value for UBase is used. Therefore, always set UBase as rated
primary phase-to-phase voltage of the protected object. If phase to neutral (PhN)
measurement is selected as setting, the operation of phase-to-earth over voltage is
automatically divided by sqrt3. This means operation for phase-to-earth voltage over:
(%)
(
) / 3
U
UBase kV
>
×
and operation for phase-to-phase voltage over:
U
(%) UBase(kV)
>
×
EQUATION1993 V1 EN-US
(Equation 72)
The below described setting parameters are identical for the two steps (n = 1 or 2). Therefore
the setting parameters are described only once.
Characteristicn: This parameter gives the type of time delay to be used. The setting can be
Definite time, Inverse Curve A, Inverse Curve B, Inverse Curve C or I/Prog. inv. curve. The choice
is highly dependent of the protection application.
OpModen: This parameter describes how many of the three measured voltages that should be
above the set level to give operation. The setting can be
1 out of 3, 2 out of 3, 3 out of 3. In
most applications it is sufficient that one phase voltage is high to give operation. If the
function shall be insensitive for single phase-to-earth faults
1 out of 3 can be chosen, because
the voltage will normally rise in the non-faulted phases at single phase-to-earth faults. In
subtransmission and transmission networks the UV function is mainly a system supervision
function and 3 out of 3 is selected.
Un>: Set operate overvoltage operation value for step n, given as % of UBase. The setting is
highly dependent of the protection application. Here it is essential to consider the maximum
voltage at non-faulted situations. Normally this voltage is less than 110% of nominal voltage.
1MRK 505 370-UEN D
Section 8
Voltage protection
Busbar protection REB670
211
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...