QB1
QB2
QC1
QA1
QC2
WA1 (A)
WA2 (B)
QA2
QC3
T
QC4
QB4
QB3
QA2 and QC4 are not
used in this interlocking
AB_TRAFO
en04000515.vsd
IEC04000515 V1 EN-US
Figure 157: Switchyard layout AB_TRAFO
M13566-4 v4
The signals from other bays connected to the module AB_TRAFO are described below.
12.4.4.2
Signals from bus-coupler
M13566-6 v4
If the busbar is divided by bus-section disconnectors into bus-sections, the busbar-busbar
connection could exist via the bus-section disconnector and bus-coupler within the other bus-
section.
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
AB_TRAFO ABC_BC
AB_TRAFO ABC_BC
(WA1)A1
(WA2)B1
(WA7)C
C
B2
A2
en04000487.vsd
IEC04000487 V1 EN-US
Figure 158: Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic for input signals concerning bus-coupler are the same as the specific
logic for the line bay (ABC_LINE):
Signal
BC_12_CL
A bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12
The switch status of BC_12 is valid.
EXDU_BC
No transmission error from bus-coupler bay (BC).
The logic is identical to the double busbar configuration “Signals from bus-coupler“.
1MRK 505 370-UEN D
Section 12
Control
Busbar protection REB670
311
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...