17.6.1.1
Functionality
M17109-38 v3
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial communication
exchanging information with a control system. In IEC terminology a primary station is a master
and a secondary station is a slave. The communication is based on a point-to-point principle.
The master must have software that can interpret the IEC 60870-5-103 communication
messages. For detailed information about IEC 60870-5-103, refer to IEC 60870 standard part 5:
Transmission protocols, and to the section 103, Companion standard for the informative
interface of protection equipment.
17.6.1.2
Design
M17109-41 v1
General
M17109-43 v2
The protocol implementation consists of the following functions:
•
Event handling
•
Report of analog service values (measurands)
•
Fault location
•
Command handling
•
Autorecloser ON/OFF
•
Teleprotection ON/OFF
•
Protection ON/OFF
•
LED reset
•
Characteristics 1 - 4 (Setting groups)
•
File transfer (disturbance files)
•
Time synchronization
Hardware
M17109-59 v2
When communicating locally with a Personal Computer (PC) or a Remote Terminal Unit (RTU)
in the station, using the SPA/IEC port, the only hardware needed is:· Optical fibers, glass/
plastic· Opto/electrical converter for the PC/RTU· PC/RTU
Commands
M17109-62 v4
The commands defined in the IEC 60870-5-103 protocol are represented in dedicated function
blocks. These blocks have output signals for all available commands according to the protocol.
For more information, refer to the
Communication protocol manual, IEC 60870-5-103.
•
IED commands in control direction
Function block with defined IED functions in control direction, I103IEDCMD. This block use
PARAMETR as FUNCTION TYPE, and INFORMATION NUMBER parameter is defined for each
output signal.
•
Function commands in control direction
Function block with pre-defined functions in control direction, I103CMD. This block includes
the FUNCTION TYPE parameter, and the INFORMATION NUMBER parameter is defined for each
output signal.
•
Function commands in control direction
Function block with user defined functions in control direction, I103UserCMD. These function
blocks include the FUNCTION TYPE parameter for each block in the private range, and the
INFORMATION NUMBER parameter for each output signal.
1MRK 505 370-UEN D
Section 17
Station communication
Busbar protection REB670
413
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...