Using PTP for synchronizing the MU
SAM600 VT
SAM600 CT
SAM600 TS
IED
PTP
9-2
IEC17000040-1-en.vsdx
IEC17000040 V1 EN-US
Figure 215: Setting example with PTP synchronization
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/
TIMESYNCHGEN:1/IEC61850-9-2:
•
HwSyncSrc: is not used as the SW-time and HW-time are connected with each other due to
PTP
•
SyncLostMode : set to Block to block protection functions if time synchronization is lost
or set to
BlockOnLostUTC if the protection functions are to be blocked when global
common synchronization is lost
•
SyncAccLevel: can be set to 1μs since this corresponds to a maximum phase angle error of
0.018 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Communication/Ethernet
configuration/Access point/AP_X:
•
Operation: On
•
PTP: On
Two status monitoring signals can be:
•
SYNCH signal on the MUx function block indicates that protection functions are blocked
due to loss of internal time synchronization to the IED
•
MUSYNCH signal on the MUx function block monitors the synchronization flag
smpSynch
in the datastream and IED hardware time synchronization.
Section 17
1MRK 505 370-UEN D
Station communication
404
Busbar protection REB670
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...