No.
StartMode
RetripMode
t1 and t2
initiated with
When t1 has
elapsed, TRRET will
When t2
has
elapsed, TRBU
will
be given if
t1 and t2
will be
stopped
(reset) if
21
LatchedStart
Always
external START
always be given
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
t1 and (t2 or t2MPh)
and 150ms expires
and current is below
set level of IPh> or
CBCLD input has
logical value zero
22
FollowStart
Off
external START
never be given
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
external START
disappears
23
FollowStart
UseFunction
Mode
external START
be given if current
is above set level
of IPh> and higher
than I>BlkCBPos
or CBCLD input
has logical value
one when current
is smaller than
I>BlkCBPos
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
external START
disappears
24
FollowStart
Always
external START
be given if
external START is
present
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
external START
disappears
25
FollowStart&
Mode
Off
external START
and current
above set level
never be given
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
current is below set
level of IPh> or
external START
disappears
26
FollowStart&
Mode
UseFunction
Mode
external START
and current
above set level
be given if current
is above set level
of IPh> and higher
than I>BlkCBPos
or CBCLD input
has logical value
one when current
is smaller than
I>BlkCBPos
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
current is below set
level of IPh> or
external START
disappears
27
FollowStart&
Mode
Always
external START
and current
above set level
be given if
external START is
present
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
current is below set
level of IPh> or
external START
disappears
Section 7
1MRK 505 370-UEN D
Current protection
190
Busbar protection REB670
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...