Setting
Short Description
Selected
value
Comments
UGenZeroDb
Zero point clamping in % of
Ubase
25
Set minimum voltage level to 25%. Voltage
below 25% will force S, P and Q to zero.
IGenZeroDb
Zero point clamping in % of
Ibase
3
Set minimum current level to 3%. Current
below 3% will force S, P and Q to zero.
UBase (set in
Global base)
Base setting for voltage level
in kV
400.00
Set rated OHL phase-to-phase voltage
IBase (set in
Global base)
Base setting for current level
in A
1000
Set rated primary CT current used for OHL
SBase (set in
Global base)
Base Setting for power base in
MVA
1000
Set based on rated Power
Table 50: Settings parameters for level supervision
Setting
Short Description
Selected
value
Comments
PMin
Minimum value
-100
Minimum expected load
PMax
Minimum value
100
Maximum expected load
PZeroDb
Zero point clamping in 0.001%
of range
3000
Set zero point clamping to 60 MW that is, 3%
of 200 MW
PRepTyp
Reporting type
db
Select amplitude deadband supervision
PDbRepInt
Cycl: Report interval (s), Db: In
0.001% of range, Int Db: In
0.001%s
2000
Set ±Δdb=40 MW that is, 2% (larger changes
than 40 MW will be reported)
PHiHiLim
High High limit (physical
value), % of SBase
60
High alarm limit that is, extreme overload
alarm, hence it will be 415 MW.
PHiLim
High limit (physical value), in %
of SBase
50
High warning limit that is, overload warning,
hence it will be 371 MW.
PLowLim
Low limit (physical value), in %
of SBase
-50
Low warning limit -500 MW
PLowLowlLim
Low Low limit (physical value),
in % of SBase
-60
Low alarm limit -600 MW
PLimHyst
Hysteresis value in % of range
(common for all limits)
1
Set ±Δ Hysteresis 20 MW that is, 1% of range
(2000 MW)
Table 51: Settings for calibration parameters
Setting
Short Description
Selected
value
Comments
IAmpComp5
Amplitude factor to calibrate
current at 5% of Ir
0.00
IAmpComp30
Amplitude factor to calibrate
current at 30% of Ir
0.00
IAmpComp100
Amplitude factor to calibrate
current at 100% of Ir
0.00
UAmpComp5
Amplitude factor to calibrate
voltage at 5% of Ur
0.00
UAmpComp30
Amplitude factor to calibrate
voltage at 30% of Ur
0.00
UAmpComp100
Amplitude factor to calibrate
voltage at 100% of Ur
0.00
Table continues on next page
1MRK 505 370-UEN D
Section 14
Monitoring
Busbar protection REB670
359
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...