arrangements up to two differential zones as shown in Section
for three one-phase IEDs.
As an example, the necessary equipment for the summation type, busbar differential
protection for a single busbar station with up to 24 bays, is shown in Figure
.
IED
with 1A
CT inputs
IB2
IX2
IA2
L1 L2 L3 N
IA1
IB1
IX1
LA
LB
LX
A-bus
Summation CTs
Main CTs
CT1
CT2 . . . CT24
IEC06000127_2_en.vsd
L1 L2 L3 N
L1 L2 L3 N
IEC06000127 V2 EN-US
Figure 82: Principle CT connections for the complete station
This summation type bus differential protection still has the same main CT requirements as
"Rated equivalent secondary e.m.f. requirements"
•
main CT ratio differences can be tolerated up to 10:1 (for example, 3000/5A CT can be
balanced against CT"s as low as 300/5)
•
different main CT ratios are compensated numerically by a parameter setting
•
main CT shall not saturate quicker than 2 ms ( refer to section
secondary e.m.f. requirements"
for detailed CT requirements regarding main CT knee-
point voltage)
However, due to the summation principle this type of busbar protection scheme has the
following limitations:
1MRK 505 370-UEN D
Section 6
Differential protection
Busbar protection REB670
135
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...