No.
StartMode
RetripMode
t1 and t2 initiated
with
When t1 has
elapsed, TRRET will
When t2 or t2MPh
has elapsed, TRBU
will be given if
t1 and t2 and
t2MPh will be
stopped (reset) if
FunctionMode = Current or CB Pos
19
LatchedStart
Off
external START
never be given
current is above
set level *) and
higher than
I>BlkCBPos or
CBCLDLx input
has logical value
one when current
is smaller than
I>BlkCBPos
t1 and (t2 or
t2MPh) and 150ms
expires and
current is below
set level *) or
CBCLDLx input
has logical value
zero
20
LatchedStart
UseFunction
Mode
external START
be given if current
is above set level
of IPh> and higher
than I>BlkCBPos or
CBCLDLx input has
logical value one
when current is
smaller than
I>BlkCBPos
current is above
set level *) and
higher than
I>BlkCBPos or
CBCLDLx input
has logical value
one when current
is smaller than
I>BlkCBPos
t1 and (t2 or
t2MPh) and 150ms
expires and
current is below
set level *) or
CBCLDLx input
has logical value
zero
21
LatchedStart
Always
external START
always be given
current is above
set level *) and
higher than
I>BlkCBPos or
CBCLDLx input
has logical value
one when current
is smaller than
I>BlkCBPos
t1 and (t2 or
t2MPh) and 150ms
expires and
current is below
set level *) or
CBCLDLx input
has logical value
zero
22
FollowStart
Off
external START
never be given
current is above
set level *) and
higher than
I>BlkCBPos or
CBCLDLx input
has logical value
one when current
is smaller than
I>BlkCBPos
external START
disappears
23
FollowStart
UseFunction
Mode
external START
be given if current
is above set level
of IPh> and higher
than I>BlkCBPos or
CBCLDLx input has
logical value one
when current is
smaller than
I>BlkCBPos
current is above
set level *) and
higher than
I>BlkCBPos or
CBCLDLx input
has logical value
one when current
is smaller than
I>BlkCBPos
external START
disappears
24
FollowStart
Always
external START
be given if external
START is present
current is above
set level *) and
higher than
I>BlkCBPos or
CBCLDLx input
has logical value
one when current
is smaller than
I>BlkCBPos
external START
disappears
Table continues on next page
Section 7
1MRK 505 370-UEN D
Current protection
182
Busbar protection REB670
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...