WA1_QA1:
•
B1QOPEN/CLD = Position of TIE_QA1 breaker and belonging disconnectors
•
B2QOPEN/CLD = Position of WA2_QA1 breaker and belonging disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting
CBConfig = 1 1/2 bus CB
TIE_QA1:
•
B1QOPEN/CLD = Position of WA1_QA1 breaker and belonging disconnectors
•
B2QOPEN/CLD = Position of WA2_QA1 breaker and belonging disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting
CBConfig = Tie CB
WA2_QA1:
•
B1QOPEN/CLD = Position of WA1_QA1 breaker and belonging disconnectors
•
B2QOPEN/CLD = Position of TIE_QA1 breaker and belonging disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting
CBConfig = 1 1/2 bus alt. CB
If only two SESRSYN functions are provided in the same IED, the connections and settings are
according to the SESRSYN functions for WA1_QA1 and TIE_QA1.
12.1.4
Setting guidelines
M12550-3 v14
The setting parameters for the Synchronizing, synchrocheck and energizing check function
SESRSYN are set via the local HMI (LHMI) or PCM600.
This setting guidelines describes the settings of the SESRSYN function via the LHMI.
Common base IED value for primary voltage ( UBase ) is set in a Global base value function,
GBASVAL, found under Main menu//Configuration/Power system/GlobalBaseValue/
GBASVAL_X/UBase. The SESRSYN function has one setting for the bus reference voltage
(
GblBaseSelBus) and one setting for the line reference voltage (GblBaseSelLine) which
independently of each other can be set to select one of the twelve GBASVAL functions used for
reference of base values. This means that the reference voltage of bus and line can be set to
different values. The settings for the SESRSYN function are found under Main menu/
Settings/IED Settings/Control/Synchronizing(25,SC/VC)/SESRSYN(25,SC/VC):X has been
divided into four different setting groups: General, Synchronizing, Synchrocheck and
Energizingcheck.
1MRK 505 370-UEN D
Section 12
Control
Busbar protection REB670
259
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...