of the switching devices are uncertain. The interlocking function uses this information for
evaluation, which means that also the interlocking conditions are uncertain.
To ensure that the interlocking information is correct at the time of operation, a unique
reservation method is available in the IEDs. With this reservation method, the bay that wants
the reservation sends a reservation request to other bays and then waits for a reservation
granted signal from the other bays. Actual position indications from these bays are then
transferred over the station bus for evaluation in the IED. After the evaluation the operation
can be executed with high security.
This functionality is realized over the station bus by means of the function blocks QCRSV and
RESIN. The application principle is shown in Figure
.
The function block QCRSV handles the reservation. It sends out either the reservation request
to other bays or the acknowledgement if the bay has received a request from another bay.
The other function block RESIN receives the reservation information from other bays. The
number of instances is the same as the number of involved bays (up to 60 instances are
available). The received signals are either the request for reservation from another bay or the
acknowledgment from each bay respectively, which have received a request from this bay. Also
the information of valid transmission over the station bus must be received.
en05000117.vsd
IED
IED
From other
SCSWI in
the bay
To other
SCSWI
in the
bay
3
Station bus
. .
.
. . .
. . .
3
RESIN
EXCH_OUT
EXCH_IN
RESIN
EXCH_OUT
EXCH_IN
..
SCSWI
RES_RQ
RES_GRT
RES_DATA
QCRSV
RES_RQ1
RES_RQ8
RES_GRT1
RES_GRT8
..
2
IEC05000117 V2 EN-US
Figure 143: Application principles for reservation over the station bus
The reservation can also be realized with external wiring according to the application example
in Figure
. This solution is realized with external auxiliary relays and extra binary inputs and
outputs in each IED, but without use of function blocks QCRSV and RESIN.
1MRK 505 370-UEN D
Section 12
Control
Busbar protection REB670
293
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...