Time-current curves
Fault Current
10
10
0.01
10000
en05000204.ai
Str
tfunc1
n
n
tfunc2
Trip time
n
IEC05000204 V2 EN-US
Figure 92: Fault time with maintained selectivity
The operation time can be set individually for each overcurrent protection. To assure
selectivity between different protective protections, in the radial network, there have to be a
minimum time difference
D
t between the time delays of two protections. The minimum time
difference can be determined for different cases. To determine the shortest possible time
difference between we must have knowledge about operation time of protections, breaker
opening time and protection resetting time. These time delays can vary significantly between
different pieces of equipment. The following time delays can be estimated:
protection operation
time:
15-60 ms
protection resetting
time:
15-60 ms
Breaker opening time:
20-120 ms
Example
Assume two substations A and B directly connected to each other via one line, as shown in the
figure below. We study a fault located at another line from the station B. The fault current to
the overcurrent protection of IED B1 has a magnitude so that the protection will have
instantaneous function. The overcurrent protection of IED A1 must have a delayed function.
The sequence of events during the fault can be described using a time axis, see figure
Section 7
1MRK 505 370-UEN D
Current protection
158
Busbar protection REB670
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...