WrnLimitTHD: It defines the warning limit for the calculated total harmonic distortion.
tDelayAlmTHD: It defines the alarm delay time from warning for the calculated total harmonic
distortion. This intimates the operator to take corrective operations immediately, otherwise
the system will undergo thermal stress.
WrnLimit2ndHD: It defines the warning limit for the calculated second harmonic distortion.
tDelayAlm2ndHD: It defines the alarm delay time from warning for the calculated second
harmonic distortion.
WrnLimit3rdHD: It defines the warning limit for the calculated third harmonic distortion.
tDelayAlm3rdHD: It defines the alarm delay time from warning for the calculated third
harmonic distortion.
WrnLimit4thHD: It defines the warning limit for the calculated fourth harmonic distortion.
tDelayAlm4thHD: It defines the alarm delay time from warning for the calculated fourth
harmonic distortion.
WrnLimit5thHD: It defines the warning limit for the calculated fifth harmonic distortion.
tDelayAlm5thHD: It defines the alarm delay time from warning for the calculated fifth
harmonic distortion.
14.11
Voltage harmonic monitoring VHMMHAI
GUID-B2F24353-AAEA-4520-BB1C-5FD5FFCFC67B v1
14.11.1
Identification
GUID-BF90E93F-C0F4-43F7-BDD5-F3C289B5535B v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage harmonic monitoring
VHMMHAI
UTHD
VTHD
14.11.2
Application
GUID-987BCB6C-C559-42EE-9AAB-5F71189A58C6 v2
In order to maintain the power quality for better supply, harmonics in the system must be
monitored. Due to the nonlinear loads connected to the system, harmonics (apart from
fundamental frequency component) are generated and thereby the system voltage is
distorted. Voltage distortion appears to have a little effect on operation of nonlinear loads
connected, either phase-to-phase or phase-to-neutral. Current distortion is limited at the
point of common coupling PCC to control the harmonic current from the utility to the
consumer. Thereby, the voltage distortion must be limited in order to prevent it from
spreading to other facilities.
Voltage harmonic distortion levels can vary drastically, depending on the configuration of
system. These voltage harmonics can damage the equipment as they are designed to operate
for certain range of voltage inaccuracy.
Moreover, in four-wire distribution systems (three-phase and neutral), the currents in the three
phases will return via the neutral conductor, a 120 degree phase shift between corresponding
phase currents that causes the currents to cancel out in the neutral, under balanced loading
conditions. When nonlinear loads are present, any ‘Triplen’ (3
rd
, 9
th
…) harmonics in the phase
currents does not cancel out. However, they will be added cumulatively in the neutral
conductor, which can carry up to 173% of phase current at a frequency of predominately 180
Hz (3
rd
harmonic).
Section 14
1MRK 505 370-UEN D
Monitoring
380
Busbar protection REB670
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...