background image

ADSx(2F) Series

DynaShield

®

Surge Protection Devices

User Manual and Installation Instruction Guide 
Surge Protection Device for AC Power Applications

Summary of Contents for DynaShield ADS 2F Series

Page 1: ...ADSx 2F Series DynaShield Surge Protection Devices User Manual and Installation Instruction Guide Surge Protection Device for AC Power Applications ...

Page 2: ...t site building DANGER ONLY QUALIFIED PERSONNEL SHOULD INSTALL OR SERVICE THIS SYSTEM ELECTRICAL SAFETY PRECAUTIONS MUST BE FOLLOWED WHEN INSTALLING OR SERVICING THIS EQUIPMENT TO PREVENT RISK OF ELECTRICAL SHOCK TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE MAKING ELECTRICAL CONNECTIONS OR SERVICING DANGER SEULEMENT LE PERSONNEL QULIFIE DOIT INSTALLER OU MAINTENIR CE SYSTEME DES PREC...

Page 3: ...s equipment To prevent risk of Electrical Shock turn off and lock out all power sources to the unit before making electrical connections or servicing General Safety This document provides detailed information on how to install and operate the ADSx Series of Surge Protection Devices SPDs IMPORTANT INSTALLATION OF THIS DEVICE SHOULD ONLY BE PERFORMED BY A LICENSED ELECTRICIAN Incorrect installation ...

Page 4: ...95 non condensing It is encouraged to avoid direct sun loading OVERCURRENT PROTECTION For ease of maintenance it is recommended that the SPD be connected to the service panel using a multi pole 20 A or 30 A circuit breaker MOUNTING The SPD uses a NEMA 4X enclosure suitable for use in indoor or outdoor installations Locate the SPD on the wall next to the service panel Locate the available disconnec...

Page 5: ... 4 in 89 mm 3 5 in 263 mm 10 4 in Figure 2 Dimensional Drawing ADSx200 2F ADSx300 2F Models MOUNTING BRACKETS ADSx models are supplied with two mounting brakets with mounting holes Attach mouting brackets to rear of unit as required by installation location B A For ADSx050 ADSx100 Models A 60 3 mm 2 4 in B 89 mm 3 5 in For ADSx200 ADSx300 Models A 100 mm 3 9 in B 130 mm 5 1 in Figure 3 Mounting Br...

Page 6: ...not carry the supply current They only conduct the short duration current associated with the suppression of transient surge events Installation Instructions Before starting the installation measure the Line voltage with an AC voltmeter to ensure the correct device has been selected for the current application The MCOV maximum continuous operating voltage must not exceed the maximum limits for the...

Page 7: ...conduit If metallic conduit is used adequate electrical continuity must be maintained at all connections including electrical enclosures Three Phase Wye 4 Wire Ground 120 208 V 127 220 V 220 385 V 240 415 V 277 480 V or 347 600V PHASE C PHASE B PHASE A 120 127 220 240 277 or 347 V NEUTRAL L N Voltage GND Requires a 3 Pole Breaker 208 220 385 415 480 or 600 V Three Phase Delta 3 Wire Ground 240V 48...

Page 8: ...crews on front of unit remove cover and turn over 2 Locate the terminal connections and connect using 18 22 AWG wires Route wires out thru pipe nipple 3 Close cover taking care not to pinch any wires or ribbon cable 4 Tighten screws Wiring for the Alarm Contacts must meet or exceed the rating of the wiring provided for the mains OPTIONAL INSTALLATION 1 It is possible for an end user to add their o...

Page 9: ...n NOTE BEFORE ENERGIZING THE SPD ENSURE ALL CONNECTIONS ARE CORRECT STATUS INDICATORS PHASE LED INDICATOR S When the SPD is securely connected and operating properly the Blue Phase LEDs will be illuminated Replacement of the SPD is required if any Blue phase LED is not illuminated Apply power The SPD is fully operational when the BLUE LED on the front panel are illuminated If the Blue LED are exti...

Page 10: ...s R NC NO Form C Contacts F EMI Noise Filter Type Part ADSx KKK VVVV O Figure 7 Part Numbering System DESCRIPTIONS ADSx 2F T KKK VVVV EL ADSx Model Name K kA Rating V Voltage Configuration O Options Delta Configurations do not come with a filter so the 2F is dropped from the part number kA Rating Surge Capacity 3 numeric charactors define the kA rating per phase Voltage Configuration 3 numeric 1 a...

Page 11: ......

Page 12: ...CORPORATE HEADQUARTERS 64 Catalyst Drive Canton North Carolina 28716 USA TEL 1 828 646 9290 EMAIL online info alltecglobal com www alltecglobal com ...

Reviews: