What to do
Cause
Fault / Aux.
code aux code
visible only on
assistant con-
trol panel and
drive com-
poser))
Code
(hex)
Check parameter 35.03 Measured
temperature 2, motor cooling and
fault limit for measured temperat-
ure 1.
Measured temperature 2
has exceeded fault limit.
External temper-
ature 2
4982
Check the cooling of the motor.
Check the motor load and drive
ratings. Check the wiring of the
temperature sensor. Repair wiring
if faulty.
Measure the resistance of the
sensor. Replace the sensor if faulty.
The CPTC-02 module indic-
ates overtemperature:
•
motor temperature is
too high, or
•
the thermistor is in
shortcircuit.
Safe motor tem-
perature
4991
See A581 Fan (page 70).
Cooling fan feedback
missing.
Fan
5080
Check auxiliary fan(s) and connec-
tion(s). Replace fan if faulty.
An auxiliary cooling fan is
stuck or disconnected.
0001 – Auxiliary fan 1
broken
0002 – Auxiliary fan 2
broken
Auxiliary fan
broken
5081
Check connection between the relay
output of the module and the STO
terminal.
Safe motor temperature
fault is generated and
STO event/fault/warning
is not generated.
SMT circuit mal-
function
5089
Contact ABB for hardware replace-
ment.
STO hardware diagnostics
detected an hardware
failure.
STO hardware
failure
5090
Check safety circuit connections
parameter 95.04 Control board
supply.
Safe torque off function
is active.
Safe torque off
5091
Contact ABB.
Power unit memory is
cleared.
PU logic error
5092
Cycle power to the drive. You may
have to repeat this.
Mismatch of drive hard-
ware and memory inform-
ation.
Rating ID mis-
match
5093
Contact ABB.
Fault in internal temperat-
ure measurement.
Measurement
circuit temperat-
ure
5094
158 Diagnostics
EN
HI
Summary of Contents for ACS560
Page 2: ......
Page 8: ...6a 6b 6a 6c 7 8 8 8 EN Quick installation and start up guide EN HI ...
Page 52: ...52 EN Quick installation and start up guide EN HI ...
Page 126: ...126 Parameter listing EN HI ...
Page 135: ... Compliance with the European Low Voltage Directive Technical data 135 EN HI ...
Page 170: ...170 ...
Page 175: ...R0 6 R5 R8 6a 6b 6c 7 R5 R8 8 R5 R8 HI त वरित इंस टालेशन और स टार ट अप गाइड 175 EN HI ...
Page 191: ...I O ABB कनेक शन आरेख HI त वरित इंस टालेशन और स टार ट अप गाइड 191 EN HI ...
Page 202: ... डिस प ले 1 I O 2 3 4 5 49 19 1 6 202 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 213: ... ve ve 2 1 OK 2 3 4 1 2 HI त वरित इंस टालेशन और स टार ट अप गाइड 213 EN HI ...
Page 216: ... 216 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 218: ...218 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 278: ...278 पैरामीटर सूची EN HI ...
Page 285: ...IP20 H1 H2 W D तकनीकी डेटा 285 EN HI ...
Page 287: ... यूरोपीय कम वोल टेज निदेश का अनुपालन तकनीकी डेटा 287 EN HI ...