8. Connect the twisted shield to the grounding terminal (6b) and the conductors
to the UDC+/R+ and R- terminals (6c).
6a
6b
6c
9. Tighten the screws to the torque given below.
R2
R0…R1
Frame size
lbf·ft
N·m
lbf·ft
N·m
0.9…1.1
1.2…1.5
0.4
0.5…0.6
UDC+/R+, R-
Finalization
10. Ground the motor cable shield at the motor end. For minimum radio frequency
interference, ground the motor cable shield 360° at the lead-through of the motor
terminal box.
14 EN - Quick installation and start-up guide