If the drive will be connected on an IT (ungrounded) system, make sure you
have disconnected the EMC filter and Varistor (VAR). See
.
1.
2.
:
•
•
2
1
3.
4.
5.
R8:
,
R8
4
86 Electrical installation
Connection procedure, frames R6…R8
WARNING!
If the drive will be connected on an IT (ungrounded) system,
make sure you have disconnected the EMC filter and ground-to-phase varistor.
See page
71
. If the drive will be connected on a corner-grounded TN system, make
sure you have disconnected the EMC filter. See page
71
.
1. Attach the residual voltage warning sticker next to the control board.
2. Remove the side plates of the cable box as follows:
•
Remove the retaining screws.
•
Slide the walls out.
3. Remove the shroud on the power cable terminals by releasing the clips with a
screwdriver and pulling the shroud out.
4. Knock out holes in the shroud for the cables to be installed.
5. Frames R8: If you install parallel cables, also knock out holes in the lower shroud
for the cables to be installed.
1
2
3
4
5
R8…R8
3
86 Electrical installation
Connection procedure, frames R6…R8
WARNING!
If the drive will be connected on an IT (ungrounded) system,
make sure you have disconnected the EMC filter and ground-to-phase varistor.
See page
71
. If the drive will be connected on a corner-grounded TN system, make
sure you have disconnected the EMC filter. See page
71
.
1. Attach the residual voltage warning sticker next to the control board.
2. Remove the side plates of the cable box as follows:
•
Remove the retaining screws.
•
Slide the walls out.
3. Remove the shroud on the power cable terminals by releasing the clips with a
screwdriver and pulling the shroud out.
4. Knock out holes in the shroud for the cables to be installed.
5. Frames R8: If you install parallel cables, also knock out holes in the lower shroud
for the cables to be installed.
1
2
3
4
5
R8…R8
3
186 HI -
त्वरित
इंस्टालेशन
और
स्टार्ट
-
अप
गाइड
EN
HI
Summary of Contents for ACS560
Page 2: ......
Page 8: ...6a 6b 6a 6c 7 8 8 8 EN Quick installation and start up guide EN HI ...
Page 52: ...52 EN Quick installation and start up guide EN HI ...
Page 126: ...126 Parameter listing EN HI ...
Page 135: ... Compliance with the European Low Voltage Directive Technical data 135 EN HI ...
Page 170: ...170 ...
Page 175: ...R0 6 R5 R8 6a 6b 6c 7 R5 R8 8 R5 R8 HI त वरित इंस टालेशन और स टार ट अप गाइड 175 EN HI ...
Page 191: ...I O ABB कनेक शन आरेख HI त वरित इंस टालेशन और स टार ट अप गाइड 191 EN HI ...
Page 202: ... डिस प ले 1 I O 2 3 4 5 49 19 1 6 202 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 213: ... ve ve 2 1 OK 2 3 4 1 2 HI त वरित इंस टालेशन और स टार ट अप गाइड 213 EN HI ...
Page 216: ... 216 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 218: ...218 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 278: ...278 पैरामीटर सूची EN HI ...
Page 285: ...IP20 H1 H2 W D तकनीकी डेटा 285 EN HI ...
Page 287: ... यूरोपीय कम वोल टेज निदेश का अनुपालन तकनीकी डेटा 287 EN HI ...