What to do
Cause
Fault / Aux.
code aux code
visible only on
assistant con-
trol panel and
drive com-
poser))
Code
(hex)
Connect motor cable.
If the drive is in scalar mode and
nominal current of the motor is less
than 1/6 of the nominal output
current of the drive, set parameter
31.19 Motor phase loss to No action
[0].
Motor circuit fault due to
missing motor connection
(any of the three phases
not connected). In scalar
control mode, the drive
detects fault only when
the output frequency is
above 10% of the motor
nominal frequency. Con-
nect motor cable. If the
drive is in scalar mode and
nominal current of the
motor is less than 1/6 of
the nominal output cur-
rent of the drive, set para-
meter 31.19 Motor phase
loss to No action [0].
Output phase
loss
3381
Check proper cooling of the drive
and auxiliary cooling fan.
Control board temperat-
ure is too high.
Control board
temperature
4110
Check ambient conditions, air flow
and fan, dust pick-up in heatsink
fins and motor power.
Estimated drive IGBT
temperature is excessive.
IGBTovertemper-
ature
4210
Check ambient temperature, air
flow and fan operation, dust pick-
up in heatsink. Clean whenever ne-
cessary.
Drive module temperature
is excessive.
Cooling
4290
Check ambient conditions, air flow
and fan, dust pick-up in heatsink
fins and motor power.
Drive IGBT temperature is
excessive.
IGBT temperat-
ure
42F1
Check ambient conditions, air flow
and fan, dust pick-up in heatsink
fins and motor power.
Power unit module temper-
ature is excessive.
Excess temperat-
ure
4310
Check motor cabling and drive
module(s) cooling.
High temperature differ-
ence between the IGBTs
of different phases.
Excess temperat-
ure difference
4380
Check parameter 35.02 Measured
temperature 1, motor cooling and
fault limit for measured temperat-
ure 1.
Measured temperature 1
has exceeded fault limit.
External temper-
ature 1
4981
Diagnostics 157
EN
HI
Summary of Contents for ACS560
Page 2: ......
Page 8: ...6a 6b 6a 6c 7 8 8 8 EN Quick installation and start up guide EN HI ...
Page 52: ...52 EN Quick installation and start up guide EN HI ...
Page 126: ...126 Parameter listing EN HI ...
Page 135: ... Compliance with the European Low Voltage Directive Technical data 135 EN HI ...
Page 170: ...170 ...
Page 175: ...R0 6 R5 R8 6a 6b 6c 7 R5 R8 8 R5 R8 HI त वरित इंस टालेशन और स टार ट अप गाइड 175 EN HI ...
Page 191: ...I O ABB कनेक शन आरेख HI त वरित इंस टालेशन और स टार ट अप गाइड 191 EN HI ...
Page 202: ... डिस प ले 1 I O 2 3 4 5 49 19 1 6 202 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 213: ... ve ve 2 1 OK 2 3 4 1 2 HI त वरित इंस टालेशन और स टार ट अप गाइड 213 EN HI ...
Page 216: ... 216 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 218: ...218 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 278: ...278 पैरामीटर सूची EN HI ...
Page 285: ...IP20 H1 H2 W D तकनीकी डेटा 285 EN HI ...
Page 287: ... यूरोपीय कम वोल टेज निदेश का अनुपालन तकनीकी डेटा 287 EN HI ...