What to do
Cause
Fault / Aux.
code aux code
visible only on
assistant con-
trol panel and
drive com-
poser))
Code
(hex)
Contact ABB.
Fieldbus adapter A map-
ping file read error.
FBA A mapping
file
6306
Reboot the control unit using para-
meter 96.08 Control board boot or
by cycling power. If the problem
persists, contact ABB.
Internal fault.
Note: This fault cannot be
reset.
Task overload
6481
Reboot the control unit. If the
problem persists, contact ABB.
Internal fault.
Stack overflow
6487
Check the auxiliary code. See ac-
tions for each code below.
Application file incompat-
ible or corrupted.
Application load-
ing
64A3
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated
by Automation Builder.
Not enough memory for
the application.
8006
Update the system library or rein-
stall
Automation Builder.
See the drive-specific log generated
by Automation Builder.
The application contains
the wrong system library
version.
8007
In Automation Builder, give a
“Clean” command and reload the
application.
The application is empty.
8008
In Automation Builder, check applic-
ation task configuration, give a
“Clean all” command, and reload
the application.
The application contains
invalid tasks.
8009
Update the system library or rein-
stall Automation Builder.
See the drive-specific log generated
by Automation Builder.
The application contains
an unknown target (sys-
tem) library function.
800A
Reboot the control unit. If the
problem persists, contact ABB.
File read error.
Internal file load
64A1
Contact ABB.
Rating ID load error.
Rating ID fault
64A4
Check the fault code extension.
Fault in adaptive program.
Adaptive pro-
gram
64A6
160 Diagnostics
EN
HI
Summary of Contents for ACS560
Page 2: ......
Page 8: ...6a 6b 6a 6c 7 8 8 8 EN Quick installation and start up guide EN HI ...
Page 52: ...52 EN Quick installation and start up guide EN HI ...
Page 126: ...126 Parameter listing EN HI ...
Page 135: ... Compliance with the European Low Voltage Directive Technical data 135 EN HI ...
Page 170: ...170 ...
Page 175: ...R0 6 R5 R8 6a 6b 6c 7 R5 R8 8 R5 R8 HI त वरित इंस टालेशन और स टार ट अप गाइड 175 EN HI ...
Page 191: ...I O ABB कनेक शन आरेख HI त वरित इंस टालेशन और स टार ट अप गाइड 191 EN HI ...
Page 202: ... डिस प ले 1 I O 2 3 4 5 49 19 1 6 202 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 213: ... ve ve 2 1 OK 2 3 4 1 2 HI त वरित इंस टालेशन और स टार ट अप गाइड 213 EN HI ...
Page 216: ... 216 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 218: ...218 HI त वरित इंस टालेशन और स टार ट अप गाइड EN HI ...
Page 278: ...278 पैरामीटर सूची EN HI ...
Page 285: ...IP20 H1 H2 W D तकनीकी डेटा 285 EN HI ...
Page 287: ... यूरोपीय कम वोल टेज निदेश का अनुपालन तकनीकी डेटा 287 EN HI ...