07 ELECTRICAL INSTALLATION
3BHS213401 E01 REV H
ACS1000 AIR-COOLED
USER MANUAL
94/184
7.5.2.2
Connections
CAUTION
⚠
- Connect the feeder cable conductors to busbars
• 1U1, 1V1, 1W1, 2U1, 2V1, 2W1 (12-pulse and 24-pulse drive, Fig. 7-9)
• 3U1, 3V1, 3W1, 4U1, 4V1, 4W1 (24-pulse drive, Fig. 7-9)
- Connect the motor cables to busbars U2, V2, W2 (Fig. 7-9).
- Connect the screens of all conductors and the shields of all cables to the PE ground busbar
(1 in Fig. 7-9).
- Connect the equipotential bonding conductor to the PE ground busbar.
- Tie the cables to the strain relief rails (2 in Fig. 7-9).
Risk of flashover!
High voltages will be present in the terminal compartment. High voltages can
cause flashover between conductors with different electric potential, and
between a conductor and earth.
Maintain the following minimum clearances:
- 20 mm between conductors
- 40 mm between a conductor and earth
Summary of Contents for ACS 1013-A1
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000 air cooled User manual ...
Page 3: ...Contents ACS1000 air cooled User manual ...
Page 5: ... 01 About this manual 01 3 14 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 15 26 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 27 50 ...
Page 53: ... 04 Control system 04 51 66 ...
Page 68: ......
Page 69: ... 05 Transportation storage and disposal05 67 74 ...
Page 76: ......
Page 77: ... 06 Mechanical installation 06 75 82 ...
Page 84: ......
Page 85: ... 07 Electrical installation07 83 106 ...
Page 108: ......
Page 109: ... 08 Commissioning 08 107 112 ...
Page 115: ... 09 Operation 09 113 126 ...
Page 129: ... 10 CDP control panel 10 127 150 ...
Page 153: ... 11 Preventive and corrective maintenance 11 151 182 ...
Page 185: ......