10 CDP CONTROL PANEL
3BHS213401 E01 REV H
ACS1000 AIR-COOLED
USER MANUAL
149/184
10.5.2
Entering a reference value
Entering a reference value from the CDP control panel is possible in:
- Local control mode
L
- Remote control mode
R
1. Press a mode selection key.
2. To enter the reference value input mode, press the REF key.
3. To enter / change the reference value, press the corresponding fast or slow navigation key.
1 L ->
600.0 rpm I
Status
Running
MotorSpeed 600.00 rpm
Power
75.0 %
ACT
PAR
FUNC
DRIVE
LOC
I
0
RESET
REF
ENTER
REM
1 L ->
[600.0 rpm] I
Status
Running
MotorSpeed 600.00 rpm
Power
75.0 %
ACT
PAR
FUNC
DRIVE
LOC
I
0
RESET
REF
ENTER
REM
1 L ->
[550.0 rpm] I
Status
Running
MotorSpeed 600.00 rpm
Power
75.0 %
ACT
PAR
FUNC
DRIVE
LOC
I
0
RESET
REF
ENTER
REM
Summary of Contents for ACS 1013-A1
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000 air cooled User manual ...
Page 3: ...Contents ACS1000 air cooled User manual ...
Page 5: ... 01 About this manual 01 3 14 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 15 26 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 27 50 ...
Page 53: ... 04 Control system 04 51 66 ...
Page 68: ......
Page 69: ... 05 Transportation storage and disposal05 67 74 ...
Page 76: ......
Page 77: ... 06 Mechanical installation 06 75 82 ...
Page 84: ......
Page 85: ... 07 Electrical installation07 83 106 ...
Page 108: ......
Page 109: ... 08 Commissioning 08 107 112 ...
Page 115: ... 09 Operation 09 113 126 ...
Page 129: ... 10 CDP control panel 10 127 150 ...
Page 153: ... 11 Preventive and corrective maintenance 11 151 182 ...
Page 185: ......