07 ELECTRICAL INSTALLATION
3BHS213401 E01 REV H
ACS1000 AIR-COOLED
USER MANUAL
90/184
7.5.1.3
Splitting multi-core cables
This section applies to drives without an additional cabinet.
- Check the distance between point of cable entry and closest busbar.
- Check the cable diameter.
- If distance and cable diameter do not allow bending the cable inside the terminal
compartment, separate the conductors outside of the terminal compartment.
Continue with:
- “7.5.1.4 Preparing cables for EMC plates” on page 90
- “7.5.1.5 Preparing cables for cable entries with sealing modules” on page 92
- “7.5.1.6 Preparing cables for cable entries with cable glands” on page 93
7.5.1.4
Preparing cables for EMC plates
As a standard, the cabinet is delivered for cable entry through the roof of the terminal
compartment. If cables are entered through the floor, swap entry plate and cover plate.
The orientation of the EMC plates is the same for cable entry through the roof and through the
floor, ie, the sealing grommets face upwards.
1. Remove the grommets.
2. To ensure proper sealing, cut along the marking that corresponds to the cable diameter.
Slide the grommet onto the cable.
Note:
The grommet must fit tightly to prevent water entering the cabinet. The grommets
can be discarded if cables are entered through the floor.
3. If necessary, remove the entry plate and push the cable through the entry holes.
Summary of Contents for ACS 1013-A1
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000 air cooled User manual ...
Page 3: ...Contents ACS1000 air cooled User manual ...
Page 5: ... 01 About this manual 01 3 14 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 15 26 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 27 50 ...
Page 53: ... 04 Control system 04 51 66 ...
Page 68: ......
Page 69: ... 05 Transportation storage and disposal05 67 74 ...
Page 76: ......
Page 77: ... 06 Mechanical installation 06 75 82 ...
Page 84: ......
Page 85: ... 07 Electrical installation07 83 106 ...
Page 108: ......
Page 109: ... 08 Commissioning 08 107 112 ...
Page 115: ... 09 Operation 09 113 126 ...
Page 129: ... 10 CDP control panel 10 127 150 ...
Page 153: ... 11 Preventive and corrective maintenance 11 151 182 ...
Page 185: ......