11 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS213401 E01 REV H
ACS1000 AIR-COOLED
USER MANUAL
174/184
11.6.11 Replacing the non-redundant fan
CAUTION
⚠
Figure 11-8: Fan location, dimensions and weight
Figure 11-9: Fan - tools and devices
1. Disconnect all power supplies to the drive and ground the drive.
2. To isolate the fan from the auxiliary power supply, switch off the motor starter of the fan.
3. Unplug the power supply cable (2 in Fig. 10-10: 1) of the fan.
4. Remove the bolts (2 in Fig. 10-10).
Note:
Do not drop washers and bolts into the cabinet.
5. Move the fan onto the lift truck by one of the following methods:
-
Place lift truck or trolley in front of the fan
: place the lift truck or height-adjustable
trolley in front of the fan and pull the fan onto the platform.
~100 kg
Heavy load!
The fan weighs approximately 100 kg.
(1) 1/4”
(2) ~70 mm
(3) 10 mm and 13 mm
(4) Trolley
(5) Lift truck
For more information, see “11.6.2 De-energizing the drive locally” on page 162.
469 mm
774 mm
868 mm
1
2
3
4
5
Summary of Contents for ACS 1013-A1
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000 air cooled User manual ...
Page 3: ...Contents ACS1000 air cooled User manual ...
Page 5: ... 01 About this manual 01 3 14 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 15 26 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 27 50 ...
Page 53: ... 04 Control system 04 51 66 ...
Page 68: ......
Page 69: ... 05 Transportation storage and disposal05 67 74 ...
Page 76: ......
Page 77: ... 06 Mechanical installation 06 75 82 ...
Page 84: ......
Page 85: ... 07 Electrical installation07 83 106 ...
Page 108: ......
Page 109: ... 08 Commissioning 08 107 112 ...
Page 115: ... 09 Operation 09 113 126 ...
Page 129: ... 10 CDP control panel 10 127 150 ...
Page 153: ... 11 Preventive and corrective maintenance 11 151 182 ...
Page 185: ......