11 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS213401 E01 REV H
ACS1000 AIR-COOLED
USER MANUAL
157/184
Example:
In the above example:
+Fault MCB Disturb
is the reason for the failure of the drive, as it occurred first.
3.
+Warn Undervoltage
occurred approx. 3 sec after the first fault.
+Fault Undervoltage
immediately followed the warning.
-Fault RESET FAULT
informs that the fault has been reset.
11.3.4
Standard troubleshooting procedure
If a fault shuts down the drive, proceed as follows:
1. -Fault RESET FAULT
2011-04-26 14:57:56.5370
2. +Fault Undervoltage
2011-04-26 14:47:41.1110
3. +Warn Undervoltage
2011-04-26 14:47:41.1000
4. +Fault MCB Disturb
2011-04-26 14:47:38.0230
For more information on alarms and faults, see
“Appendix G - Signal and parameter table”.
1. Do not switch off the auxiliary supply voltage or try to reset a fault message
before all information at the time of the occurrence of the fault condition has
been saved.
2. Select the fault history display on the CDP control panel, but do not clear the
buffer!
For more information, see “10 CDP control panel” on page 127.
3. Identify the fault and make a logbook entry.
4. Save the content of the data logger when a PC is available that has the
DriveWindow or DriveDebug tool installed.
The data logger provides information (eg, waveforms of voltage, current,
torque) for efficient troubleshooting.
5. Contact ABB service if a fault cannot be rectified.
When calling ABB service, it is recommended to have the following data available
at the time when the fault occurred:
- Operating, ambient and load conditions
- Unusual events
6. After the fault has been rectified, start the drive as described in “09
Summary of Contents for ACS 1013-A1
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000 air cooled User manual ...
Page 3: ...Contents ACS1000 air cooled User manual ...
Page 5: ... 01 About this manual 01 3 14 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 15 26 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 27 50 ...
Page 53: ... 04 Control system 04 51 66 ...
Page 68: ......
Page 69: ... 05 Transportation storage and disposal05 67 74 ...
Page 76: ......
Page 77: ... 06 Mechanical installation 06 75 82 ...
Page 84: ......
Page 85: ... 07 Electrical installation07 83 106 ...
Page 108: ......
Page 109: ... 08 Commissioning 08 107 112 ...
Page 115: ... 09 Operation 09 113 126 ...
Page 129: ... 10 CDP control panel 10 127 150 ...
Page 153: ... 11 Preventive and corrective maintenance 11 151 182 ...
Page 185: ......