ZKTECO White LCD Serials User Manual
- 106 -
Device status
There are three options: Control-in, control-out and none
Control-in: When it is set, the verified record on the device is in-record.
Control-out: When it is set, the verified record on the device is
out-record.
None: When it is set, close the device’s anti-pass back function.
3. Modify device’s Wiegand output format
If the two devices are communicating, only Wiegand signals without
device ID can be received. Enter device Menu -> Comm. Opt ->
Wiegand option or enter software:
Basic setting -> device management
-> Wiegand
, to modify “defined format” as “wiegand26 without device
ID”.
4. Enroll user
The user must be on master machine and slave machine at the same time,
and user PIN must be the same. Therefore, it is necessary to enroll user
on master machine and slave machine at the same time.
5. Connection instruction
Wiegand communication is adopted for master machine and slave
machine. Refer to the following for connection:
Master Slave
IND0 <-----> WD0
IND1 <-----> WD1
GND <-----> GND