Chapter 5: Technical specifications
80
ZP1-F Series Installation Manual
Table 35: Supervised inputs
[1]
Cable resistance
Short circuit
Active
High-impedance fault
Standby
Open circuit
≤ 220 Ω
< 220 Ω to 8 kΩ
< 8 kΩ to 10 kΩ
< 10 kΩ
to 20 kΩ
> 20 kΩ
Note: For EN 54-13 compliance, the active
impedance should be from 220
Ω
to 3.9
kΩ.
Sourced current
1 mA max. (for activation with short-circuit
contact)
Voltage between terminals
28 V max. (for deactivation with open circuit)
[1] Fire routing acknowledgement inputs
Table 36: Output specifications
Output termination
Class B outputs (default)
Class A outputs
15 kΩ 5% end
-of-line resistor
4.7 k
Ω 1/4W 1% end
-of-line resistor
Sounder/fire routing/fault warning outputs [1]
Supervised
Current per output (two-four-zone)
Current per output (eight-zone)
Voltage in standby (EN 54-13 disabled)
Voltage in standby (EN 54-13 enabled)
Voltage in alarm
For open and short circuit
250 mA max.
500 mA max. at 25ºC
385 mA max. at 40ºC
−11.5 VDC max.
−8.4 VDC max.
+21 VDC min.
+28 VDC max.
Alarm relay output
Number of potential-free outputs
Commutation current
1
2 A at 30 VDC max.
Fault relay output
Number of potential-free outputs
Commutation current
Default state
1
2 A at 30 VDC max.
Energized (fail to safe)
Auxiliary 24 VDC output
Voltage
Current
24 VDC nominal
28 VDC max.
21 VDC min.
250 mA max.
[1] The number of available outputs depends on the control panel model, supervision type, and
operating mode. See “Operating mode presets” on page 90 for more information.
Содержание ZP1-F2
Страница 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Страница 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Страница 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Страница 92: ...Chapter 5 Technical specifications 86 ZP1 F Series Installation Manual Figure 23 Eight zone cabinet with cover...
Страница 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Страница 113: ......