Appendix A: Configuration presets
ZP1-F Series Installation Manual
93
BS 5839-1
Table 53: Configuration presets
Preset Control panel EOL type
Output type
Sounder
outputs
[1]
Zone type
11
Two-zone
Active
Class B
2 (stage 1 “Alert”) Mixed
11
Four-zone,
eight-zone
Active
Class B
4 (stage 1 “Alert”) Mixed
12
Two-zone
Active, CleanMe
enabled [2]
Class B
2 (stage 1 “Alert”) Mixed
12
Four-zone,
eight-zone
Active, CleanMe
enabled [2]
Class B
4 (stage 1 “Alert”) Mixed
13
Two-zone
Active
Class B
2 (stage 2
“Evacuation”)
Mixed
13
Four-zone,
eight-zone
Active
Class B
4 (stage 2
“Evacuation”)
Mixed
14
Two-zone
Active, CleanMe
enabled [2]
Class B
2 (stage 2
“Evacuation”)
Mixed
14
Four-zone,
eight-zone
Active, CleanMe
enabled [2]
Class B
4 (stage 2
“Evacuation”)
Mixed
[1] Stage 1 “Alert”: sounders off during any configured sounder delay.
Stage 2 “Evacuation”: sounders intermittent during any configured sounder delay.
[2] The CleanMe feature is not available for Ziton devices.
Table 54: Additional configuration characteristics
Default sounder delay
0
Default zone delay
0n
Start/Restart sounders
Start sounders or restart stopped sounders at Operator user
level with or without a fire alarm event
Table 55: Inputs and outputs
INPUT1
Class change
INPUT2
Delays off
OUT1
Sounder circuit
OUT2
Sounder circuit
OUT3
Sounder circuit
OUT4
Sounder circuit
Note: Two-zone control panels have only two outputs with EN 54-13 disabled (OUT1 and OUT2)
or a single output with EN 54-13 enabled (OUT1/2).
Содержание ZP1-F2
Страница 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Страница 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Страница 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Страница 92: ...Chapter 5 Technical specifications 86 ZP1 F Series Installation Manual Figure 23 Eight zone cabinet with cover...
Страница 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Страница 113: ......