Chapter 3: Configuration and commissioning
38
ZP1-F Series Installation Manual
Sounder delay
Note:
Use this menu to configure evacuation sounder delays in NBN S 21-100
mode.
Use this menu to configure a sounder delay of up to 10 minutes in operating
modes where the feature is available.
Default delays
Default sounder delays for each operating mode are shown below.
Table 21: Default sounder delay values
Operating mode
Default delay in minutes
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
BS 5839-1
00
NBN S 21-100
01
NEN 2535
This feature is not available in this operating mode.
To configure a delay:
1. Set the display as shown below, and then press Enter.
The Sounder Delay LED flashes quickly to indicate that the sounder delay
configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Once configured the delay must be enabled at Operator user level.
To enable a configured delay:
1. Exit Installer user level.
2. Enter the Operator user level password.
3. Press the Sounder Delay button.
A steady Sounder Delay LED indicates that the delay is enabled.
Содержание ZP1-F2
Страница 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Страница 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Страница 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Страница 92: ...Chapter 5 Technical specifications 86 ZP1 F Series Installation Manual Figure 23 Eight zone cabinet with cover...
Страница 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Страница 113: ......