Chapter 3: Configuration and commissioning
ZP1-F Series Installation Manual
59
Table 26: Expansion board A configuration options
Display
Description
Value
Module A function
01 to 92 [1]
Module A output 1 delay
00 to 10 minutes
Module A output 2 delay
00 to 10 minutes
Module A output 3 delay
00 to 10 minutes
Module A output 4 delay
00 to 10 minutes
[1] Available values depend on the type of expansion board installed and the supervision
selected. See Appendix A “Configuration presets” on page 89.
Expansion board function
Use this menu to configure the expansion board function. The default value
depends on panel configuration. For most configurations, the default value is 01.
For two-zone panels, or panels configured for EN 54-13, the default is 05. For the
available presets, see Appendix A “Configuration presets” on page 89.
To configure the expansion board function:
1. Set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED on the control panel interface and the
ON LED on the expansion board flashes fast to indicate that the module
function configuration menu is active.
2. Select a value from 01 to 92 using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Содержание ZP1-F2
Страница 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Страница 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Страница 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Страница 92: ...Chapter 5 Technical specifications 86 ZP1 F Series Installation Manual Figure 23 Eight zone cabinet with cover...
Страница 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Страница 113: ......