Chapter 3: Configuration and commissioning
ZP1-F Series Installation Manual
39
Sounder outputs delay operation
The delay applies to the activation of sounder outputs only if
all
of the following
are true:
• The delay is enabled
• The initiating device (detector or manual call point) is installed in an automatic
zone or the initiating device is a detector installed in a mixed zone
• The initiating device is configured in a zone with delays configured (by
default)
• Any input using the
delays off
function must not be active
If the delay is not enabled, the control panel activates sounder outputs
immediately after the detection of the fire alarm.
Fire routing delay
Note:
Use this menu to configure warning sounder delays in NBN S 21-100
mode.
Use this menu to configure a fire routing delay of up to 10 minutes in operating
modes where the feature is available.
Default delays
The default fire routing delay for each operating mode is shown below.
Table 22: Default fire routing delay values
Operating mode
Default delay in minutes
EN 54-2 Scandinavia
01
NEN 2535
01
EN 54-2
NBN S 21-100
00
EN 54-2 Evacuation
BS 5839-1
This feature is not available in these operating modes.
To configure a delay:
1. Set the display as shown below, and then press Enter.
The Fire Routing Delay LED flashes fast to indicate that the fire routing delay
configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
Содержание ZP1-F2
Страница 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Страница 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Страница 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Страница 92: ...Chapter 5 Technical specifications 86 ZP1 F Series Installation Manual Figure 23 Eight zone cabinet with cover...
Страница 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Страница 113: ......