Chapter 3: Configuration and commissioning
ZP1-F Series Installation Manual
31
Common configuration tasks
To enter configuration mode:
1. Remove the control panel cover so that the seven-segment display is visible.
2. Enter a valid Installer user level password (3333 for basic configuration or
4444 for advanced configuration).
3. Press Enter.
When first entering configuration mode, the Mode LED on the seven-segment
display is steady. For other indications see Table 17 on page 30.
To select a menu:
1. Select the required menu using the menu selection buttons (1 and 3).
2. Press Enter.
When a configuration menu has been selected, the Value LED on the seven-
segment display is steady.
To select a value:
1. Select the required value using the value selection buttons (2 and 4).
2. Press Enter.
To exit configuration mode and save your changes:
1. Press Panel Silence.
2. Press Enter.
— or —
1. Set the display as shown below, and then press Enter.
The Panel Silence LED flashes to confirm that a configuration change has been
applied.
Note:
Make all the configuration changes required before exiting configuration
mode and saving your changes.
Содержание ZP1-F2
Страница 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Страница 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Страница 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Страница 92: ...Chapter 5 Technical specifications 86 ZP1 F Series Installation Manual Figure 23 Eight zone cabinet with cover...
Страница 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Страница 113: ......