Chapter 3: Configuration and commissioning
ZP1-F Series Installation Manual
47
Sounder re-sound
Use this menu to configure the sounder re-sound, on or off. This determines
sounder operation in a fire alarm event when sounders have been silenced by
pressing the Sounder Start/Stop button and a new alarm event is reported. The
default setting is ON.
To configure the sounder re-sound:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes fast to indicate that the sounder re-
sound configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
The sounders re-sound if a new fire alarm event is
reported from a different zone.
The sounders do not re-sound if a new fire alarm event
is reported from a different zone.
Note: For new fire alarm events in the same zone, sounders will always re-
sound if the first alarm is reported by a detector and the new alarm is
reported by a manual call point.
Содержание ZP1-F2
Страница 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Страница 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Страница 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Страница 92: ...Chapter 5 Technical specifications 86 ZP1 F Series Installation Manual Figure 23 Eight zone cabinet with cover...
Страница 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Страница 113: ......