Chapter 3: Configuration and commissioning
ZP1-F Series Installation Manual
41
Extended fire routing delay
Use this menu to configure an extended fire routing delay of up to 10 minutes in
operating modes where the feature is available.
Default delays
The default extended fire routing delay for each operating mode is shown below.
Table 23: Extended fire routing delay default values
Operating mode
Default delay in minutes
EN 54-2 Scandinavia
03
NEN 2535
03
EN 54-2
00
EN 54-2 Evacuation
BS 5839-1
NBN S 21-100
This feature is not available in these operating modes.
To configure an extended delay:
1. Set the display as shown below, and then press Enter.
The Fire Routing Delay LED flashes fast to indicate that the fire routing delay
configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
This value must be greater than the configured fire routing delay.
3. Press Enter.
4. Save your changes.
Once configured the delay is enabled at the same time as the standard fire
routing delay.
A steady Fire Routing Delay LED indicates that all configured fire routing delays
are enabled.
Extended fire routing delay operation
The same conditions required to apply a fire routing delay are applicable to apply
an extended fire routing delay (i.e. delay enabled, automatic alarm in a zone with
delays configured, no fire routing inhibit delay input activated, and no input using
the delays off function activated).
If the conditions exist to apply the delay, fire routing and extended fire routing
delays elapse concurrently when a fire alarm event is reported. After an alarm
condition, the fire routing delay is the active delay to activate fire routing.
Содержание ZP1-F2
Страница 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Страница 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Страница 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Страница 92: ...Chapter 5 Technical specifications 86 ZP1 F Series Installation Manual Figure 23 Eight zone cabinet with cover...
Страница 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Страница 113: ......