Chapter 3: Configuration and commissioning
ZP1-F Series Installation Manual
33
Basic configuration
The default password for basic configuration is 3333. After entering the
password, the first displayed menu will be Basic default configuration (indicating
basic installer user level). For more information see “User level passwords and
indications” on page 28.
The basic configuration menu
Configuration options for this menu are shown in the table below. More
information for each option is included in the related topic.
Table 19: The basic configuration menu
Display
Menu
Values
Operating mode
Basic default configuration See topic
All
EN 54-13 supervision
ON/OFF
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
NBN S 21-100
NEN 2535
Custom
Panel mode
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
BS 5839-1 (No 2nd stage)
BS 5839-1 (2nd stage)
NBN S 21-100
NEN 2535
Custom
All
Sounder delay
(or Evacuation sounder
delay for NBN S 21-100
mode)
00 to 10 minutes
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
NBN S 21-100
Fire routing delay
(or Warning sounder delay
for NBN S 21-100 mode)
00 to 10 minutes
EN 54-2
EN 54-2 Scandinavia
NBN S 21-100
NEN 2535
Extended fire routing delay 00 to 10 minutes
EN 54-2
EN 54-2 Scandinavia
NEN 2535
Add an expansion board
[1]
00 to 04 modules
All
Fire network identifier [2]
00 to 32
All
Содержание ZP1-F2
Страница 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Страница 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Страница 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Страница 92: ...Chapter 5 Technical specifications 86 ZP1 F Series Installation Manual Figure 23 Eight zone cabinet with cover...
Страница 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Страница 113: ......