Appendix A: Configuration presets
ZP1-F Series Installation Manual
95
NEN 2535
Table 59: Configuration presets
Preset Control
panel
EOL type
Output
type
Sounder
outputs
Fire routing
outputs
Zone type
31
Four-zone,
eight-zone
Passive
Class B
2
2
Odd: Automatic
Even: Manual
31
Four-zone,
eight-zone
EN 54-13
supervision
Class A
1
1
Odd: Automatic
Even: Manual
Table 60: Additional configuration characteristics
Default fire routing delay
1 minute
Default extended fire routing
delay
3 minutes
Default zone delay
ON
Start/Restart sounders
Start sounders only if there is a fire alarm
Table 61: Inputs and outputs
Input/Output
Standard
EN 54-13
INPUT1
Fire routing inhibit delay
Fire routing acknowledgement
(type 1, 100 seconds)
INPUT2
Delays off
Fault warning output open
supervision
OUT1
Sounder circuit
Sounder circuit
OUT2
Sounder circuit
OUT3
Fire routing (automatic)
Fire routing
OUT4
Fire routing (manual)
Note:
A supervised expansion board is required for fire protection and fault
warning outputs. An additional (optional) supervised expansion board may be
installed for individual automatic and manual fire routing outputs.
Содержание ZP1-F2
Страница 1: ...ZP1 F Series Installation Manual P N 501 415603 1 60 ISS 12DEC22...
Страница 78: ...Chapter 3 Configuration and commissioning 72 ZP1 F Series Installation Manual...
Страница 82: ...Chapter 4 Maintenance 76 ZP1 F Series Installation Manual...
Страница 92: ...Chapter 5 Technical specifications 86 ZP1 F Series Installation Manual Figure 23 Eight zone cabinet with cover...
Страница 94: ...Chapter 5 Technical specifications 88 ZP1 F Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 F Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 F Series Installation Manual...
Страница 113: ......