MSC-3 Instruction Manual
E030 ARs ALLOWED
E030 ARs ALLOWED
0
Range: 0...15 attempted restarts
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
This number indicates how many times the MSC-3 will attempt to restart after a trip. For the motor to
run after the trip is cleared, the drive must be given a valid run command. Select 0 restarts in order to
deactivate Auto Restart.
E031 AR CLR TIME
E031 AR CLR TIME
1200 secs
Range: 1...1200 seconds
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
If the MSC-3 operates for the
E031 A/R CLR TIME
without any trips, the number of restarts is reset to
the value of
E030 A/Rs ALLOWED.
Set the
E031 A/R CLR TIME
to 6 secs for infinite auto restarts
E04 Reset by PF
E04 Reset by PF
> DISABLED
Available Choices:
ENABLED
DISABLED
• Press
once to begin.
• Use the
▲
/
▼
buttons to enable or disable reset by power fail operation.
• Press
to confirm the choice.
When enabled trips may be cleared without any extra wiring simply by turning the power off and straight
back on again before the drive powers down completely.