IM00120
53
IM00120
MSC-3 Instruction Manual
C012 RESUME
C010 MIN Hz
C011 IDLE
Output
Speed
Reference
Speed
Time
MSC-3 is idle
Key configuration parameters are:
• C010 MIN Hz
• C011 IDLE DELAY
• C012 RESUME Hz
Line Contactor Start Control
The MSC-3 can be optionally configured so that it is powered by a
customer supplied
external 24V
DC supply independent of the mains power supply. In this mode the MSC-3 is capable of controlling an
external line contactor to apply mains power to its own power circuits. The MSC-3 remains operational
if either or both 24V DC or mains power is present. In order to control the external line contactor, one of
the MSC-3’s relays must be configured with the “AUX_PWR” function. The diagram below illustrates the
wiring.