C011 IDLE DELAY
C011 IDLE DELAY
0 secs
Range: 0…600secs
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
The
C011 IDLE DELAY
sets the time interval of operation at minimum speed before the MSC-3 enters
the idle state. Refer to “Minimum Speed Idle Function” for details.
C012 RESUME Hz
C012 RESUME Hz
0 Hz
Range: 0…200 Hz
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
The
C012 RESUME Hz
is the speed reference threshold above which the MSC-3 resumes normal
operation from being idle. If the value for
C012 RESUME Hz
is less than the
C010 MIN Hz
value, the idle
function is disabled and the MSC3 will operate at or above the
C010 MIN Hz
speed indefinitely. . Refer
to “Minimum Speed Idle Function” for details.
C02 MAX Hz
C02 MAX Hz
50 Hz
Range: C010 MIN Hz+5Hz…200 Hz
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
The
C012 RESUME Hz
is the speed reference threshold above which the MSC-3 resumes normal
operation from being idle. If the value for
C012 RESUME Hz
is less than the
C010 MIN Hz
value, the idle
function is disabled and the MSC3 will operate at or above the
C010 MIN Hz
speed indefinitely.