MSC-3 Instruction Manual
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
The G113 Signal MAX parameter is the maximum signal input used for spanning and has units of the
signal source selected by G111 AN OUT sel. See the Analogue Outputs feature for details.
G114 MIN Output & G154 MIN Output
G114 MIN Output
> 0.0 V
Range: 0.0...10.0 V or 0.0 to 20 mA
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
If the G110 AN OUT mode is configured for > Volts then G114 MIN Output will be displayed with units
of volts (V) otherwise G114 MIN Output will be displayed with units of milliamps (mA). In either case
the minimum output for spanning is determined by this parameter. See the Analogue Output feature for
details.
G115 MAX Output & G155 MAX Output
G115 MAX Output
> 5.0 V
Range: 0.0...10.0 V or 0.0 to 20 mA
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
If the G110 AN OUT mode is configured for > Volts then G115 MAX Output will be displayed with units
of volts (V) otherwise G115 MAX Output will be displayed with units of milliamps (mA). In either case
the maximum input for spanning is determined by this parameter. See the Analogue Output feature for
details.
G16 EIA/RS-485
The MSC-3 has as standard EIA/RS-485 communications with the following features:
Choice of protocol: BACNET / MODBUS.
Selectable data rates.
Selectable parity checking.
Hardware Isolation.
Optional line termination included.
G160 Protocol