IM00120
106
IM00120
MSC-3 Start Up
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
If the
G100 Input Type
is configured for
> Volts
then
G101 MIN input
will be displayed with units of
volts (V) otherwise
G101 MIN input
will be displayed with units of milliamps (mA). In either case the
minimum input for spanning is determined by this parameter. See the Analogue Inputs and Spanning
feature for details.
G102 MAX Input & G142 MAX Input
G102 MAX input
> 10.0 V
Range: 0.0...10.0 V or 0.0 to 20 mA
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
If the
G100 Input Type
is configured for
> Volts
then
G102 MAX
input will be displayed with units of
volts (V) otherwise
G102 MAX input
will be displayed with units of milliamps (mA). In either case the
maximum input for spanning is determined by this parameter. See the Analogue Inputs and Spanning
feature for details.
G103 Ref @MIN in & G143 Ref @ MIN in
G103 Ref @MIN in
0.0%
Range: -100.0...100.0 % of C03 MAX Hz
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
Regardless of how the analogue input is configured the minimum reference for input spanning is
determined by this parameter. The
G103 Ref @MIN
in parameter corresponds to the
G101 MIN
input to define the input spanning configuration. See the Analogue Inputs and Spanning
feature for details.
G104 Ref @MAX in & G144 Ref @ MAX in
G04 Ref @MAX In
100.0%
Range: -100.0...100.0 % of C03 MAX Hz
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
Содержание MSC-3