IM00120
10
IM00120
Installation
Fuse Circuit Breaker Ratings for All MSC-3 Models
Model Numbers
Chassis Size
Maximum RMS
Input Current
Recommended Fuse
or C/B Rating (A)
UL Class Fuse for UL
compliant installation (A)†
MSC-3*3
A
4.1
10
10A, Class J
MSC-3*5
A
6.9
10
10A, Class J
MSC-3*7
A
9.6
16
15A, Class J
MSC-3*11
A
15.1
20
120A, Class J
MSC-3*15
B
22.5
32
30A, Class T
MSC-3*23
B
33.0
40
40A, Class T
MSC-3*30
B
43.1
63
60A, Class T
MSC-3*40
B
55.0
63
60A, Class T
MSC-3*55
C
78.0
100
100A, Class T
MSC-3*82
C
108.0
125
125A, Class T
MSC-3*109
C
148.0
160
175A, Class T
MSC-3*140
C
179.0
200
200A, Class T
MSC-3*170
C
187.0
200
200A, Class T
MSC-3R220
D
231.0
259
250A, Class T
MSC-3R260
D
270.0
320
320A, Class T
MSC-3R315
D
336.0
400
400A, Class T
MSC-3R360
D
370.0
400
400A, Class T
MSC-3R390
D
397.0
630
630A, Class T
MSC-3R430
D
434.0
630
630A, Class T
MSC-3R490
D
516.0
630
630A, Class T
* L, R or J for Chassis A and B, L or R for Chassis C to specify supply voltage - see page 133 for
details.
† The fuse
class
referred to here is the American designation fuse required for a UL compliant
installation. this should not be confused with the British
Type
T etc designation, which refers to an
entirely different kind of fuse.
Motor thermal protection
The MSC-3 provides an electronic type thermal overload function that relies on the measured motor
current to estimate the thermal conditions of the motor. For complete motor thermal protection,
microtherms or thermistors should be installed in the motor winding and wired to the appropriate trip
relay. MSC-3 Extended Features Option provides a thermistor relay function and other features.