IM00120
25
IM00120
MSC-3 Instruction Manual
STEP 4
Follow the instructions on page 47 for MSC-3 startup, setting the parameters
according to the table below. Alternate values may be used to suit the application.
See the H00 PID Control beginning on page 113 for additional information on PID
configuration and tuning.
Menu
Menu Item
Suggested Setting
Page for detailed
information
G00 INPUT/OUTPUT
G01 Inpt fxn CFG
(Input terminal
configuration)
I00 FWD & LATCH = D3(4) (default)
90
I02 ~STOP = D2(3) (default)
91
I07 RESET = D1(2) (default
92
I11 REMOTE = D4(5) (default)
93
G00 INPUT/OUTPUT
G03 RL1
G030 RL1 Signal = RUN (default)
98
G04 Rl2
G040 RL2 Signal = TRIP (default)
100
B00 MOTOR
B01 MOTOR VOLTS
Motor nameplate voltage
71
B02 MOTOR AMPS
Motor nameplate amps
71
B03 MOTOR HZ
Motor nameplate frequency
71
B04 MOTOR RPM
Motor nameplate RPM
72
D00 PROTECTION
D01 CURRENT LIM
Motor nameplate c10%
78
D02 I2t Thermal overload
Motor nameplate current
78
E00 STOP/START
E03 AUTO RESTART
E030 ARs ALLOWED = 5
82
E04 Reset by PF
ENABLED
83
F00 REFERENCES
F01 REMOTE REF
PID OUTPUT
85
F10 PRESETS
F100 PRESET 1 = required pressure (as % of transducer full scale)
88
H00PID Control
H06 SV Choice
F100 Preset 1
114
H07 PV Choice
AI(32,34)
115
C00 PERFORMANCE
C03 RAMP
C030 ACCEL TIME = 1 sec
74
C031 DECEL TIME = 1 sec
74
STEP 5
Now connect the wire to terminal 6.
End of Procedure
Содержание MSC-3
Страница 1: ...MSC 3 Instruction Manual INVENTIVE TECHNOLOGY DSP II...
Страница 3: ......
Страница 6: ...IM00120 iv IM00120...
Страница 14: ......
Страница 59: ...IM00120 45 IM00120 MSC 3 Instruction Manual Extended Features Option Wiring...
Страница 60: ......
Страница 157: ......