MSC-3 Start Up

C04 FLUX PLUS

The MSC-3 uses a sensorless flux vector control algorithm to control the motor operation. This control 
algorithm provides independent control of motor flux throughout the speed range and is highly robust 
against motor parameter changes. It uses the motor nameplate parameters entered in the B00 MOTOR 
menu as the basis for its calculations to produce the correct flux in the motor. For a motor to produce 
full torque it must have the correct flux applied to it. This is particularly critical at low speed. Flux Plus 
adjusts the motor flux estimate to provide additional control where specific adjustments to the motor 
torque response are required.

C040 FLUX PLUS

C040 FLUX PLUS
     0.0%

Range:   

0 to 150% of adjustment range

•  Press 

   to edit the value.

•  Press 

 to make changes to the value.

•  Press 

   to accept the new value OR

•  Press 

ESC

 to abandon the value change.

This feature enables an adjustment in the flux vector algorithm that can increase motor flux to produce 
more torque for the same motor current. The amount of extra torque produced will vary from motor to 
motor depending on motor size, efficiency and the operating speed. Increase the value to produce more 
torque. This should be done in small steps to ensure the drive does not go into Current Limit. If the drive 
does go into current limit decrease the Flux Plus value slightly. This is the maximum torque that the 
motor can produce.

C041 HiSpd Flux+

C041 HiSPD FLUX+
     DISABLED

Available Choices: 

ENABLED

 DISABLED

•  Press 

   once to begin.

•  Use the 

 / 

 buttons to enable or disable the high speed flux plus.

•  Press 

   to confirm the choice.

When disabled the flux plus decreases with increasing speed. This allows more efficient operation of 
the MSC-3 on loads that have a high starting torque but do not require any extra torque during normal 
operation. If your load requires high torque throughout the entire speed range then enable 

C041 HiSpd 

Flux+.

Содержание MSC-3

Страница 1: ...MSC 3 Instruction Manual INVENTIVE TECHNOLOGY DSP II...

Страница 2: ...ensure compliance with all regulations and practices covering the installation and wiring of your MSC 3 The instruction manual should be completely read and understood before attempting to connect or...

Страница 3: ......

Страница 4: ...to suit different environmental conditions for improved life expectancy and reliability Ratings at 40 C 45 C and a 50 C rating are available IP30 ENCLOSED Painted enclosure with IP30 rating for mounti...

Страница 5: ...without a DC Bus Choke Line with a DC Bus Choke REMOTE DISPLAY PANEL Remote Display Kit which allows remote access to programming menu and drive controls An IP66 rating applies if fitted correctly Ava...

Страница 6: ...IM00120 iv IM00120...

Страница 7: ...MC compliance 13 Control connections and configuration 19 General 19 Factory default settings 19 Settings for your application 19 Quick Setup 19 Industrial Terminals Typical Connection Diagram Termina...

Страница 8: ...ng tower fan with reverse acting internal PID 61 Application Water pumping with automatic pressure control 61 Communications 62 EIA RS 485 Communication Indicator 62 BACnet MS TP 62 BACnet Services Su...

Страница 9: ...y Units 68 Load Factory Defaults 69 Load Custom Defaults 69 Save Custom Defaults 70 Upload Download Connection 70 B00 MOTOR Menu 70 B01 MOTOR VOLTS 71 B02 MOTOR AMPS 71 B03 MOTOR Hz 71 B04 MOTOR RPM 7...

Страница 10: ...R CLR TIME 83 E04 Reset by PF 83 E05 Motor Resync 84 E06 LC CONTROL 84 F00 REFERENCES Menu 84 F01 REMOTE 85 F02 LOCAL 85 F03 ESO 86 F04 JOGFWD 86 F05 JOG REV 86 F06 USER REF 1 and F07 USER REF 2 86 F0...

Страница 11: ...G03 RL1 15 16 98 Relay Output Functions 98 G030 RL1 Signal 98 G031 RL1 Sense 99 G032 RL1 TON 99 G033 RL1 TOFF 99 G04 RL2 17 18 100 G040 RL2 Signal 100 G041 RL2 Sense 100 G042 RL2 TON 100 G043 RL2 TOFF...

Страница 12: ...min 108 G113 Signal max G153 Signal max 108 G114 MIN Output G154 MIN Output 109 G115 MAX Output G155 MAX Output 109 G16 EIA RS 485 109 G160 Protocol 109 G161 bits sec 110 G162 Parity 110 G163 MAC Dev...

Страница 13: ...em Settings 120 Appendix A BACnet Protocol Application Layer Description 120 Objects and Properties Supported 120 Analog Values 121 Accumulators 121 Binary Values 122 Appendix B MODBUS Protocol Applic...

Страница 14: ......

Страница 15: ...inals disconnect all sources of electrical power wait at least 11 minutes for capacitors within the MSC 3 to discharge to less than 50VDC and then ensure by measurement that there is no hazardous AC o...

Страница 16: ...tain circumstances The overall application machine etc must be designed such that automatic restart is not hazardous Do not install this equipment in locations where mechanical damage to the enclosure...

Страница 17: ...SC 3 must be mounted vertically No other mounting orientation is acceptable If the MSC 3 is mounted inside another enclosure the total heat dissipation and resulting temperature rise in the enclosure...

Страница 18: ...allation Information C D A B F E G G Bolt Diameter Bolt Diameter Chassis A IP30 NEMA 1 3 11 Amps A C D E B F G G Bolt Diameter Bolt Diameter Chassis A IP66 NEMA 4 3 11Amps CAUTION Allow 50mm above bel...

Страница 19: ...MSC 3 11 Chassis A IP30 NEMA 1 With DC Choke 248mm 9 8 102mm 4 309mm 12 2 208mm 8 2 32mm 1 3 230mm 9 1 6mm 0 25 7 2Kg 16lbs MSC 3 3 MSC 3 5 MSC 3 7 MSC 3 11 Chassis A IP66 NEMA 4 310mm 12 2 190mm 7 5...

Страница 20: ...0 47 42Kg 92lbs 62Kg 136lbs MSC 3 82 Chassis C All types 715mm 28 1 470mm 18 5 290mm 11 4 625mm 24 6 330mm 13 677mm 26 7 12mm 0 47 44Kg 97lbs 64Kg 141lbs MSC 3 109 Chassis C All types 715mm 28 1 470mm...

Страница 21: ...or ventilation Model Enclosure type Dimensions tolerance 1 0mm Weight with choke A B C D E F G MSC 3R220 Chassis D All types 1225mm 48 2 555mm 21 9 525mm 20 7 1132mm 44 6 300mm 11 8 1185mm 46 7 12mm 0...

Страница 22: ...el Enclosure type Dimensions tolerance 1 0mm Weight with choke and stand E G H I J K L M P MSC 3R220 Chassis D All types as per previous page 618mm 4 3 459mm 18 1 659mm 25 9 475mm 18 7 425mm 16 7 13mm...

Страница 23: ...rough in the unlikely but possible event of a major arcing fault in wiring or within MSC 3 enclosure Installations that are required to be UL compliant must use UL listed fuses of the amp rating and c...

Страница 24: ...15 D 336 0 400 400A Class T MSC 3R360 D 370 0 400 400A Class T MSC 3R390 D 397 0 630 630A Class T MSC 3R430 D 434 0 630 630A Class T MSC 3R490 D 516 0 630 630A Class T L R or J for Chassis A and B L o...

Страница 25: ...ply The single phase supply voltage must be within the 3 phase supply voltage limits for the MSC 3 model to be used For example use an MSC 3Lxx model for a 240VAC single phase supply or a MSC 3Rxx mod...

Страница 26: ...y be used with a DC supply There are a number of issues to be considered in properly applying MSC 3 in this situation some of which involve the characteristics of the particular DC supply to be used P...

Страница 27: ...motor will have a significant impact on the overall EMC result achieved in any given installation The EMC performance of an installation will usually be dominated by the lowest performance section of...

Страница 28: ...n See gland plate detail on left for control cable exit location AC supply screened cable not required Screened power cable Motor isolation switch if required Metal enclosure Metal cable gland with 36...

Страница 29: ...lation switch if required Metal enclosure Screened power cable Motor terminal box metal Metal cable gland with 360 screen termination Screened control cable No special EMC requirement here Plastic or...

Страница 30: ...re Screened power cable Motor terminal box metal Metal cable gland with 360 screen termination Screened control cable No special EMC requirement here Plastic or other cable gland may be used Metal cab...

Страница 31: ...al enclosure Screened power cable Motor terminal box metal Metal cable gland with 360 screen termination Screened control cable No special EMC requirement here Metal cable gland with 360 screen termin...

Страница 32: ...l cable gland with 360 screen termination Metal enclosure Motor isolation switch if required Screened power cable AC supply screened cable not required Screened control cable No special EMC requiremen...

Страница 33: ...control from either the terminal strip or the front panel console as selected by a local remote input on the terminal strip This is detailed as Config 1 starting on page 20 There is a menu function t...

Страница 34: ...s I07 RESET D1 I02 STOP D2 I00 FWD LATCH D3 I11 REMOTE D4 Optional Wiring If selection between local and remote is not required place a link between terminals 1 and 5 If the output disable is not requ...

Страница 35: ...ntrol 2 wire control Power up start MSC 3 will start as soon as power is applied i Local Remote Selection The Local Remote Selection can be used in conjunction with any of the above circuits Wire term...

Страница 36: ...the type of input signal mA or voltage Set G021 Min Input and G022 MAX Input to reflect the range of the signal typically 4 20mA or 0 10V For more information see page 89 MSC 3 Control Board 8 9 10 11...

Страница 37: ...93 G00 INPUT OUTPUT G03 RL1 G030 RL1 Signal RUN default 98 G04 Rl2 G040 RL2 Signal TRIP default 100 B00 MOTOR B01 MOTOR VOLTS Motor nameplate voltage 71 B02 MOTOR AMPS Motor nameplate amps 71 B03 MOTO...

Страница 38: ...own CAUTION Do not connect the wire to terminal 6 yet The terminal configuration should not be changed while the MSC 3 is enabled 5V D1 D2 D3 D4 EN COM SCN MSC 3 Control Board Water pressure transduce...

Страница 39: ...RL1 G030 RL1 Signal RUN default 98 G04 Rl2 G040 RL2 Signal TRIP default 100 B00 MOTOR B01 MOTOR VOLTS Motor nameplate voltage 71 B02 MOTOR AMPS Motor nameplate amps 71 B03 MOTOR HZ Motor nameplate fr...

Страница 40: ...s Wire terminals 5 and 6 as shown In local the MSC 3 is stopped and started from the front panel console In remote the MSC 3 stop start is controlled from the terminal strip The source of the speed re...

Страница 41: ...the type of input signal mA or voltage Set G021 Min Input and G022 Max Input to reflect the range signal typically 4 20mA or 0 10V For more information see page 89 MSC 3 Control Board 8 9 10 11 IN Vre...

Страница 42: ...T OUTPUT G03 RL1 G030 RL1 Signal RUN default 98 G04 Rl2 G040 RL2 Signal TRIP default 100 B00 MOTOR B01 MOTOR VOLTS Motor nameplate voltage 71 B02 MOTOR AMPS Motor nameplate amps 71 B03 MOTOR HZ Motor...

Страница 43: ...g according to the instructions on pages 9 to 18 STEP 2 Connect your control wiring as shown CAUTION Do not connect the wire to terminal 6 yet The terminal configuration should not be changed while th...

Страница 44: ...the arrows to display the options Press Enter when AI910 11 is displayed Press ESC Go tot the G00 INPUT OUTPUT menu and select G02 AI 10 11 Set G020 for the type of input signal mA or voltage Set G02...

Страница 45: ...default 100 B00 MOTOR B01 MOTOR VOLTS Motor nameplate voltage 71 B02 MOTOR AMPS Motor nameplate amps 71 B03 MOTOR HZ Motor nameplate frequency 71 B04 MOTOR RPM Motor nameplate RPM 72 D00 PROTECTION D0...

Страница 46: ...configuration applicable to pump and fan drives in the HVAC industry Typically these will be controlled from an external speed signal frequently supplied from the output of a building management syst...

Страница 47: ...s shown The Local Remote selection can be overridden from the control console See Remote Override Operation on page 102 In local the MSC 3 is stopped and started from the front panel console In remote...

Страница 48: ...or the type of input signal mA or voltage Set G021 Min Input and G022 Max Input to reflect the range signal typically 4 20mA or 0 10V For more information see page 89 MSC 3 Control Board 8 9 10 11 IN...

Страница 49: ...0 RL2 Signal TRIP default 100 B00 MOTOR B01 MOTOR VOLTS Motor nameplate voltage 71 B02 MOTOR AMPS Motor nameplate amps 71 B03 MOTOR HZ Motor nameplate frequency 71 B04 MOTOR RPM Motor nameplate RPM 72...

Страница 50: ...e instructions on page 47 for MSC 3 startup setting the parameters according to the table below Alternate values may be used to suit the application Menu Menu Item Suggested Setting Page for detailed...

Страница 51: ...n page 47 for MSC 3 startup setting the parameters according to the table below Alternate values may be used to suit the application Menu Menu Item Suggested Setting Page for detailed information G00...

Страница 52: ...wn CAUTION Do not connect the wire to terminal 6 yet The terminal configuration should not be changed while the MSC 3 is enabled 1 2 3 4 5 6 7 8 9 10 11 5V D1 D2 D3 D4 EN COM SCN Vref IN IN MSC 3 Cont...

Страница 53: ...MOTOR VOLTS Motor nameplate voltage 71 B02 MOTOR AMPS Motor nameplate amps 71 B03 MOTOR HZ Motor nameplate frequency 71 B04 MOTOR RPM Motor nameplate RPM 72 D00 PROTECTION D01 CURRENT LIM Motor namep...

Страница 54: ...gnal wiring from the external PID controller as shown Consult the PID controller manufacturer s literature for other connections and power supples required by the PID controller STEP 4 Follow the inst...

Страница 55: ...onnect the wire to terminal 6 yet The terminal configuration should not be changed while the MSC 3 is enabled 1 2 3 4 5 6 7 8 9 10 11 5V D1 D2 D3 D4 EN COM SCN Vref IN IN MSC 3 Control Board MSC 3 Ext...

Страница 56: ...71 B02 MOTOR AMPS Motor nameplate amps 71 B03 MOTOR HZ Motor nameplate frequency 71 B04 MOTOR RPM Motor nameplate RPM 72 D00 PROTECTION D01 CURRENT LIM Motor nameplate current 10 78 D02 I2t Thermal o...

Страница 57: ...e a standard two pair shielded instrumentation cable Internally this will have a total of 4 conductors physically arranged as two twisted pairs surrounded by an aluminium wrapper as a screen A bare dr...

Страница 58: ...Avoid laying communication cables adjacent to power cabling and wiring If not possible utilise the best separation of communication cabling and power cabling Communication cables should cross power c...

Страница 59: ...IM00120 45 IM00120 MSC 3 Instruction Manual Extended Features Option Wiring...

Страница 60: ......

Страница 61: ...the MSC 3 before running the motor to present any unexpected motor operation The MSC 3 is supplied with a link between the EN terminal and the 5V terminal which is all that is required to run the MSC...

Страница 62: ...r details The example shows that the desired output speed is 50 Hz and the motor is rotating at 25 Hz in the forward direction in local mode as indicated by the status TheMSC 3 was started by pressing...

Страница 63: ...ach Meter Display facet is viewed by pressing the button Note Each example display is shown with the EIA RS 485 communication indicator Refer to the previous section for details 25 0Hz 11 4kW 8 0A 750...

Страница 64: ...of linear ramp Ramp time with S time set to 0 01 Ramp time with S time set to a value greater than zero The motor accelerates at a rate of B03 MOTOR Hz C030 ACCEL TIME and decelerates at a rate of B0...

Страница 65: ...is a building air conditioning application in which a fan is required to operate as part of a smoke clearance system Various standards for example AS NZS 1668 1 1998 The use of ventilation and air co...

Страница 66: ...t Only competent personnel should undertake this work CAUTION Any use of the Essential Services Override feature should be arranged to comply with all local rules and regulations concerning the partic...

Страница 67: ...so that it is powered by a customer supplied external 24V DC supply independent of the mains power supply In this mode the MSC 3 is capable of controlling an external line contactor to apply mains pow...

Страница 68: ..._ PWR relay function will then operate the input line contactor charging the MSC 3 When charging is complete the motor is run as required The AUX_PWR relay will open if The drive experiences a trip Th...

Страница 69: ...5 High Low High F105 Preset 6 High High Low F106 Preset 7 High High High F107 Preset 8 The diagram below illustrates this feature Selected Reference I16 Selector 1 I18 Selector 3 I17 Selector 2 F06 US...

Страница 70: ...ith adjustable thresholds The diagram below illustrates the design G020 AN IN mode G025 HiCMP Level G025 LoCMP Level Hi AN IN Lo AN IN COM Vref IN IN Output Analogue Input Circuitry reference G021 MIN...

Страница 71: ...output for those applications that require feedback of an internal signal The analogue output is designed with the following features Configurable voltage V or current mA input configuration Signal so...

Страница 72: ...6 SV choice H07 PV choice Intergral gain Integrator Proportional gain Differential gain Differentiator Output clamp PID Output Reference choice H04 Opt clamp H05 Opt clamp Transducer Process Analogue...

Страница 73: ...over configuration PID Setup Checklist and Tuning 1 Control Wiring Assumes factory defaults are loaded WARNING All wiring must be done while the MSC3 is disconnected from the power supply Refer to th...

Страница 74: ...use 2 7 Perform any PID parameter adjustments e g H01 PB H02 Ti sec r etc 2 8 To close the loop the running mode reference Remote Local ESO JOGFWD or JOGREV must be set to PID Output 3 Tuning CAUTION...

Страница 75: ...r this application This setup is for a typical HVAC stair pressurisation fan application that requires air pressure control using an air pressure transducer and PID controller function provided by the...

Страница 76: ...ed EIA RS 485 protocol Communication flashing 25 0 Hz 50 0 FWD LOC Indicates he selected EIA RS 485 protocol is communicating with the network BACnet MS TP The MSC 3 BACnet interface implements the st...

Страница 77: ...he network system the reference to select is COMMS_REF Essential services operation ESO ESO mode selection from all sources wired terminal or BACnet binary object ESO is honoured at all times CAUTION...

Страница 78: ...03 Read Holding Registers Function Code 04 Read Input Registers Function Code 05 Write Single Coil Function Code 06 Write Single Register Function Code 07 Read Exception Status Function Code 08 Diagn...

Страница 79: ...s from all sources terminal strip internal MSC 3 functions and MODBUS are honoured at all times Network Speed Reference If the speed reference for the MSC3 in any given mode is to be determined by the...

Страница 80: ...he active set of parameters to the Commissioned defaults Saving a current set of parameters to commissioned defaults allows further parametric changes to be made for testing or temporary operations pu...

Страница 81: ...nd set point value The PID Meter facet helps to relate the motor speed output power and motor current to the Process variable The kWhrs Hours Run facet displays the accumulated kWhrs to the motor and...

Страница 82: ...confirm the choice The set scale will be used when the run display is on show The decimal point location is determined by A030 Run Display Format setting A032 Run Display Units A032 Run Display Units...

Страница 83: ...sing the button will cause the following message to appear CONTINUE WITH FACTORY LOAD Press again to load factory defaults as the current set of parameters OR Press ESC to continue with the existing s...

Страница 84: ...es to the MSC 3 and its application This menu provides a way to save the current set of parameters as the Custom Defaults Save Custom Defaults By loading custom defaults the MSC 3 may be restored to a...

Страница 85: ...ess to edit the value Press to make changes to the value Press to accept the new value OR Press ESC to abandon the value change The value entered is taken from the motor nameplate and is an important...

Страница 86: ...oustic performance C01 MINIMUM Hz Parameters found in this menu set the performance of features related to minimum output Hz including the minimum speed idle function C010 MIN Hz C010 MIN Hz 0 Hz Rang...

Страница 87: ...is the speed reference threshold above which the MSC 3 resumes normal operation from being idle If the value for C012 RESUME Hz is less than the C010 MIN Hz value the idle function is disabled and th...

Страница 88: ...e value Press to make changes to the value Press to accept the new value OR Press ESC to abandon the value change The C031 DECEL TIME is the time taken for the motor to go from motor rated speed down...

Страница 89: ...rates this feature C010 MIN Hz Speed Time Reference Slope B03 MOTOR Hz C032 S TIME Slope B03 MOTOR Hz C030 ACCEL TIME Slope B03 MOTOR Hz C031 DECEL TIME C034 ESO RAMP C034 ESO RAMP 10 0 sec Range 0 5...

Страница 90: ...s ESC to abandon the value change This feature enables an adjustment in the flux vector algorithm that can increase motor flux to produce more torque for the same motor current The amount of extra tor...

Страница 91: ...e synchronous speed Flux Plus may be used in conjunction with Slip Comp to provide increase output torque at low speeds C06 AUDIBLE FREQ C06 AUDIBLE FREQ 2kHz Available Choices 2kHz 4kHz 8kHz 16kHz AU...

Страница 92: ...load When the estimated heating exceeds I2t setting the drive will trip on I2t For a motor running at 110 of its I2t current this will take approximately two minutes The time to trip will shorten the...

Страница 93: ...zero Hz D021 I2t zero Hz 40 0 Amps Range 18 D020 I2t value Press to edit the value Press to make changes to the value Press to accept the new value OR Press ESC to abandon the value change This sets t...

Страница 94: ...pply voltage should be at least 1 414 times higher than the motor voltage D05 1 Phase Inpt D05 1 Phase Inpt DISABLED Available Choices ENABLED DISABLED Press once to begin Use the buttons to enable or...

Страница 95: ...dit the value Press to make changes to the value Press to accept the new value OR Press ESC to abandon the value change This sets the centre or main frequency to skip D061 SKIP RANGE D061 SKIP RANGE 0...

Страница 96: ...ice Dynamic Braking provides the means for dissipating the motor regenerative energy into an external resistor This may be required when the MSC 3 experiences regenerative currents from an overhauling...

Страница 97: ...200 secs Range 1 1200 seconds Press to edit the value Press to make changes to the value Press to accept the new value OR Press ESC to abandon the value change If the MSC 3 operates for the E031 A R C...

Страница 98: ...peration Press to confirm the choice This function mobilises internal logic to control an external mains supply contactor The external contactor is driven whenever a motor start is required and so mus...

Страница 99: ...F106 PRESET7 F107 PRESET8 REF SELECT ZERO REF Press once to begin Use the buttons to select a reference Press to confirm the choice When the drive is operating in remote mode the MSC 3 will take its...

Страница 100: ...REMOTE Press once to begin Use the buttons to select a reference Press to confirm the choice When the drive is operating in jog forward mode the MSC 3 will take its speed reference from the selected...

Страница 101: ...mode is active if neither stop reset nor persistent mode is active Stop Reset mode sets the console reference to zero whenever the MSC 3 is powered on or when commanded to stop running the motor Persi...

Страница 102: ...the F09 COMMS PRESET parameter value See G168 Comms Lost Time on page 112 for further details Setting G168 Comms Lost Time to zero disables the detection of communications loss F10 PRESETS There are...

Страница 103: ...h D1 2 Active high level is selected D1 2 Active low level is selected D1 2 Active rising edge is selected D1 2 Active falling edge is selected For all the sub menus of G01 Inpt fxn CFG the available...

Страница 104: ...ATCH D3 4 I11 REMOTE D4 5 The operator decides to have EXTERNAL WARNING activated by D4 5 That is I13 EXTERN WARN D4 5 When the operator presses the ENTER push button to make the selection the followi...

Страница 105: ...ntact closure on this input will start the motor in the reverse direction When the input is removed the motor continues to run in the reverse direction latching It requires I02 STOP function to be ass...

Страница 106: ...to 5V Both I03 FWD I04 REV inputs must be wired to 5 to activate bipolar operation D03 REVERSE must be Enabled for the motor to run backwards I05 UP I05 UP OFF Available Choices See the list of the G...

Страница 107: ...s to select a digital signal source Press to confirm the choice ESC to abandon the change Contact closure on this input will run the motor forward at the JOGFWD speed It will also clear any latched in...

Страница 108: ...a trip and the status message EX ALARM is displayed I13 EXTERN WARN I13 EXTERN WARN OFF Available Choices See the list of the G01 Inpt fxn CFG menu Press once to begin input selection Use the buttons...

Страница 109: ...C 3 is equipped with a single analogue input as standard and can be configured to receive either 0 to 5V 0 to 10V or 0 to 20mA Additionally the input has a customisable span as well as a high and low...

Страница 110: ...otherwise G022 MAX input will be displayed with units of milliamps mA In either case the maximum input for spanning is determined by this parameter See the Analogue Inputs and Spanning feature for det...

Страница 111: ...s to the value Press to accept the new value OR Press ESC to abandon the value change If the G020 Input Type is configured for Volts then G025 Hi Compare Level will be displayed with units of volts V...

Страница 112: ...UNDER SPEED threshold OVER SPD The motor speed is above the G051 OVER SPEED threshold ON The relay is energised OPT ALARM The drive output current is more than 12 5 of motor rated current A R FAIL Al...

Страница 113: ...the change This menu allows relay 1 to be inverse acting for those applications that need inverted contact behaviour G032 RL1 TON G032 RL1 TON 0 secs Range 0 600 seconds Press to edit the value Press...

Страница 114: ...cifications G040 RL2 Signal G040 RL2 Signal RUN Available choices See the list for Relay Output Functions Press once to begin input selection Use the buttons to select the output function for relay 2...

Страница 115: ...r their operation Parameters include under and over speed thresholds and calibration points for the percentage load warning output function G050 UNDER SPEED G050 UNDER SPEED 20 0 Range 0 0 100 0 of C0...

Страница 116: ...characteristic curve of fans and pumps The calibrated characteristic is used as the compare threshold to warn of possible failures in motor and load mechanics The output of the load warning feature i...

Страница 117: ...3 T2 mode below for details G071 T1 mode G073 T2 mode G071 T1 Mode Delay ON G073 T2 Mode Delay OFF Available Choices Delay ON Delay OFF Press to edit the value Press to make changes to the value Press...

Страница 118: ...t function for the digital output operation Press to confirm the choice ESC to abandon the change G081 DO Sense G121 DO Sense G081 DO Sense Direct Available Choices DIRECT INVERT Press once to begin i...

Страница 119: ...and TH terminals is greater than approximately 3300 ohms G10 AI 32 34 G14 AI 52 54 An extra analogue input is available when the MSC 3 is fitted with an extended features option This extra analogue in...

Страница 120: ...layed with units of volts V otherwise G102 MAX input will be displayed with units of milliamps mA In either case the maximum input for spanning is determined by this parameter See the Analogue Inputs...

Страница 121: ...vel the compare output will be true high See the Analogue Inputs and Spanning feature for details G106 Lo Compare Level G146 Lo Compare Level G106 Lo Compare Level 2 0 V Range 0 0 10 0 V or 0 0 to 20...

Страница 122: ...vel units of Amps LOAD Motor loading units of CURRENT Motor current units of Amps POWER Inverter output power units of kW Press once to begin input selection Use the buttons to select the output signa...

Страница 123: ...units of milliamps mA In either case the minimum output for spanning is determined by this parameter See the Analogue Output feature for details G115 MAX Output G155 MAX Output G115 MAX Output 5 0 V...

Страница 124: ...9200 bits sec Available choices 115200 bits sec 76800 bits sec 57600 bits sec 38400 bits sec 19200 bits sec 9600 bits sec 4800 bits sec 2400 bits sec 1200 bits sec Press once to begin input selection...

Страница 125: ...w value OR Press ESC to abandon the value change Each device on an EIA RS 485 network requires a unique Media Access Control Identification address code MAC ID The MAC ID is used to identify the MSC 3...

Страница 126: ...able Choices ENABLED DISABLED Press once to begin Use the buttons to enable or disable communication network termination Press to confirm the choice The MSC 3 has a no touch communication cable termin...

Страница 127: ...tiator D components For example H01 PB is 300 0 the gain is 100 300 0 333 That is 3 units of input will generate 1 unit of output H02 Ti sec r H02 Ti sec r 2 0 sec r Range 0 0 40 0 sec r Press to edit...

Страница 128: ...0 Range 100 0 100 0 Press to edit the value Press to make changes to the value Press to accept the new value OR Press ESC to abandon the value change The H04 Opt clamp and H05 Opt clamp values determ...

Страница 129: ...lable characters 0 9 A Z a Z punctuation characters Press and the character to enter begins to flash Press to move through the list of available characters Press to select the displayed character the...

Страница 130: ...ac Vbc 416 1 Vac This display reveals the Vab Vbc mains input magnitude measurement Vbus display Vbus 605 2V OK Vin P F 416 1V OK if Vbus min Vbus blank otherwise if Vin_peak min Vin_peak blank otherw...

Страница 131: ...ple T2 is not involved The heat sink temperature is the maximum value of all sensors displayed with the symbol Digital Input Display This display makes it possible to view the state of the digital inp...

Страница 132: ...ed Feature cards are viewable The state of the analogue and thermistor input are revealed on the Extended Features Analogue Input Display An example input display of an Extended Features Card fitted t...

Страница 133: ...ng meters kWhr Hours Run Press the button once to begin pass code entry The following display will appear ENTER Code 9999 The code to access the menus is fixed to 1470 Press the button once to begin U...

Страница 134: ...Object Name Object Type Description Location System Status Vendor Name Vendor Identifier Model Name Firmware Revision Application Software Version Protocol Version Protocol Revision Protocol Services...

Страница 135: ...er speed Set point for under speed alarm C AV9 Over speed Set point for over speed alarm C AV10 Speed Motor speed RPM R AV11 Speed Motor speed R AV12 Frequency VFD output frequency Hz R AV13 Load Load...

Страница 136: ...tatus Coasting Clear R BV11 ARfailed Auto Restart Status AUTO RESTART FAILED Ready R BV12 OPTSC Output Short Status OUTPUT SHORT Clear R BV13 Overvoltage Over Voltage Trip OVERVOLTAGE Clear R BV14 Ove...

Страница 137: ...ower failure trip detected 13 OverTempTrip Power hardware over temperature trip detected 14 I2tTrip Over current trip detected 15 Tripped one or more trips detected 16 Voltage Limit MSC 3 operating at...

Страница 138: ...left 10 mA or V 18 1 opANIN R Extended features analog input reading right 10 mA or V The Scaling instruction of this table will covert a raw signed 16 bit integer to a decimal value in the given unit...

Страница 139: ...the given units to a raw signed 16 bit integer Function Codes Function Code 01 Read Coils Function Code 02 Read Discrete Inputs Function Code 03 Read Holding Registers Function Code 04 Read Input Regi...

Страница 140: ...2 bytes 0 to 20 Quantity of coils 2 bytes 1 to 21 Response Function code 1 byte 2 Byte count 1 byte 1 to 3 Coil status 1 to 3 bytes MSC 3 discrete input states Error Function code 1 byte 130 128 funct...

Страница 141: ...e 1 2 or 3 Function Code 05 Write Single Cell Request Function code 1 byte 5 Output address 2 bytes 0 to 4 Output value 2 bytes 0x0000 or 0xFF00 Response Function code 1 byte 5 Output address 2 bytes...

Страница 142: ...10 Clear counters and diagnostic register 0 11 Return network message count 0 12 Return network communication error count 0 13 Return network exception error count 0 14 Return slave message count 0 1...

Страница 143: ...tion Code 16 Write Multiple Holding Registers Request Function code 1 byte 16 Starting address 2 bytes 0 to 9 Quantity of registers 2 bytes 1 to 10 Byte count 1 byte 2 x Quantity of registers Register...

Страница 144: ...or minor Revision Object byte count 1 byte Object data Object byte count bytes 1 MODBUS Encapsulated Interface Error Function code 1 byte 171 128 function code 0xAB Exception code 1 byte 1 2 or 3 Exce...

Страница 145: ...AILURE All input phases on the input power supply are either low or missing OVER CURRENT The output current has exceeded the MSC 3 s intermittent output current rating INV OVER TEMP One or more power...

Страница 146: ...direction selected in remote mode IDLE LOC The MSC 3 is idle in local mode FWD LOC The MSC 3 is running in the FWD direction in local mode REV LOC The MSC 3 is running in the REV direction in local mo...

Страница 147: ...c Logic Low 0 to 2Vdc Analog Input Vref and COM 5Vdc Supply 5mA max current IN and IN Differential Input 0 to 5V range 0 to 10V range 0 to 20mA range 4 to 20mA range Common mode range 25 Vdc to COM Re...

Страница 148: ...0A 480V 18 000A 480V 18 000A 480V 18 000A 480V 18 000A 480V 18 000A 480V 18 000A 480V 18 000A 480V 18 000A 480V 18 000A 480V 20 20 20 20 60 60 60 60 200 200 200 200 200 J J J J T T T T T T T T T 10 A...

Страница 149: ...40 3 34 1 51 1 MSC 3 55 55 0 46 6 69 9 MSC 3 82 82 0 68 9 104 3 MSC 3 109 109 92 0 138 6 MSC 3 140 140 116 9 178 0 MSC 3 170 170 132 6 199 0 MSC 3R220 220 170 0 242 0 MSC 3R260 260 200 0 286 0 MSC 3R3...

Страница 150: ...FWD or a REV terminal has been assigned and that it is at 5V with respect to DIG COM If the reverse direction is selected ensure that reverse is enabled from the Protection menu Speed signal is not c...

Страница 151: ...erdrive the motor If necessary fit dynamic braking OT message Ventilation problem Ensure operating ambient temperature is within specification Check fans are rotating freely and there is no build up o...

Страница 152: ...1200 E04 Reset by PF DISABLED E05 Motor Resync DISABLED E06 LC CONTROL DISABLED F01 REMOTE AI 10 11 F02 LOCAL CONSOLE F03 ESO F105 Preset 6 F04 JOGFWD F105 Preset 6 F05 JOGREV F105 Preset 6 F06 USER...

Страница 153: ...AX Output 5 0 G120 DO Function RUN G121 DO Sense DIRECT G122 ON Delay 0 G123 OFF Delay 0 G13 TH 37 38 DISABLED G140 Input Type Volts G141 MIN Input 0 0 G142 MAX Input 10 0 G143 Ref MIN in 0 0 G144 Ref...

Страница 154: ...Chassis A IP30 NEMA 1 175 x 335 x 145mm 6 9 x 13 2 x 5 7in 3 6Kg Choke only MSC 3 3 MSC 3 5 MSC 3 7 MSC 3 11 Chassis A IP66 NEMA 4 330 x 387 x 380mm 13 x 15 2 x 15in 7 1Kg 10Kg MSC 3 15 MSC 3 23 MSC...

Страница 155: ...ctrical electronics technology IN IN These are the designations of differential analog inputs on the MSC 3 The MSC 3 will respond to the difference between the two inputs rather than the voltage betwe...

Страница 156: ...nctions UL Underwriters Laboratories Inc An American organization involved in product safety standards and certification Variable Torque A load characteristic in which the driving torque requirement i...

Страница 157: ......

Страница 158: ...tric Pty Limited 2014 IM00120 26 October 2014 ZENER ELECTRIC PTY LIMITED ACN 001 595 428 366 Horsley Rd Milperra NSW 2144 Australia PO Box 347 Milperra NSW 2144 Australia Tel 61 2 97953600 Fax 61 2 97...

Отзывы: