IM00120
102
IM00120
MSC-3 Start Up
The
G051 OVER SPEED
parameter is a motor frequency compare threshold. When the motor frequency
is above this value, the relay will energise. For example the
> OVER SPEED
relay function has been
assigned to relay #2
(G040 RELAY #2 = OVER SPEED)
and
G051 OVER SPEED
is set to 80%. When
the output frequency goes above 80%, relay 2 will energise.
G052 %L WARNING
G052 %L WARNING
Available Choices:
> Low Speed Cal
> High Speed Cal
• Press
once to begin input selection.
• Use the
▲
/
▼
buttons to select low or high speed calibration.
• Press
to calibrate.
ESC
to abandon the change.
This menu calibrates the %load V speed characteristic curve of fans and pumps. The calibrated
characteristic is used as the compare threshold to warn of possible failures in motor and load
mechanics. The output of the %load warning feature is available as a relay function. The procedure for
calibration is:
1. Run the MSC-3 at half of full speed
2. Find the
G052 %L WARNING
menu, press
and select
> Low Speed CAL
3. Press
again to calibrate at low speed
4. Run the MSC-3 at or near full speed
5. Return to the
G052 %L WARNING
menu, press
and select
> High Speed CAL
6. Press
again to calibrate at high speed
7. Ensure
>% LOAD WARNING
function is assigned to one of the available relays
G06 REMOTE OVRD
G060 REMOTE OVRD
> DISABLED
Available Choices:
ENABLED
DISABLED
• Press
once to begin.
• Use the
▲
/
▼
buttons to enable or disable remote override operation.
• Press
to confirm the choice.