IM00120
112
IM00120
MSC-3 Start Up
Necessary for BACnet applications only, G165 Max Masters is a parameter for the BACnet MS/TP
connection logic. The value of G165 Max Master specifies the highest allowable MAC ID for master
devices. This value should be the same as that found in other MS/TP masters on the network segment.
G166 RUN SIGNALS
G166 RUN SIGNALS
> FROM TERMINALS
Available Choices:
FROM TERMINALS
FROM NETWORK
• Press
once to begin.
• Use the
▲
/
▼
buttons to select the source of run command signals.
• Press
to confirm the choice.
This parameter determines explicitly where the FWD and REV command signals are sourced. Set G166
RUN SIGNALS to FROM TERMINALS when hardwired dedicated switches or push buttons are required
to start the MSC-3. Set G166 RUN SIGNALS to FROM NETWORK when commands sent through the
communication network are required to start the MSC-3.
G167 Terminator
G167 Terminator
> DISABLED
Available Choices:
ENABLED
DISABLED
• Press
once to begin.
• Use the
▲
/
▼
buttons to enable or disable communication network termination.
• Press
to confirm the choice.
The MSC-3 has a “no-touch” communication cable termination capability. Set G167 Terminator to
ENABLED to make the line termination active. Set G167 Terminator to DISABLED to make the line
termination in-active.
G168 Comms Lost Time
G168 Comms Lost
Time: 10 secs
Range: 1...600 secs
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
The MSC-3 will determine a loss of communications if no data exchange takes place for the interval
specified by G168 Comms Lost Time parameter.
For MODBUS, any data packet addressed to the MSC-3 and free of transmission errors will reset the
timer and the timing interval will begin again.
For BACnet, a token pass addressed to the MSC-3 and free of transmission errors will reset the timer
and the timing interval will begin again.
Setting
G168 Comms Lost Time
to zero disables the detection of communications loss. See also
F09
COMMS PRESET
on page 88.
Содержание MSC-3
Страница 1: ...MSC 3 Instruction Manual INVENTIVE TECHNOLOGY DSP II...
Страница 3: ......
Страница 6: ...IM00120 iv IM00120...
Страница 14: ......
Страница 59: ...IM00120 45 IM00120 MSC 3 Instruction Manual Extended Features Option Wiring...
Страница 60: ......
Страница 157: ......