IM00120
26
IM00120
Control connections and configuration
Quick Setup for Terminal Config 4.
Features
Forward and reverse operation controlled from pushbuttons. Selection between Local
and Remote by a switch contact closure.
Procedure
STEP 1.
Complete the power wiring according to the instructions on pages 9 to 18
STEP 2.
Connect your control wiring as shown.
CAUTION
Do not connect the wire to terminal 6 yet.
The terminal configuration should not be changed while the MSC-3 is enabled.
i
Local / Remote Selection
The Local/Remote Selection can be used in
conjunction with any of the above circuits. Wire
terminals 5 and 6 as shown.
In “local” the MSC-3 is stopped and started from
the front panel console. In “remote”, the MSC-3
stop / start is controlled from the terminal strip.
The source of the speed reference in both modes
may be independently configured to come from
a wide variety of sources including the terminal
strip, console up/down buttons, preset values
and the output of optional features such as the
PID controller and networked communications
1
2
3
4
5
6
Local
Remote
+5V D1 D2 D3 D4 EN
MSC-3 Control Board
1
2
3
4
5
6
+5V D1 D2 D3 D4 EN
MSC-3 Control Board
Stop
Forward
Reverse
i
The function of terminals D1...4
are programmable. In this
configuration (Terminal config
4), the following functions are
assigned to the terminals:
I02
~ STOP
D1
I00
FWD & LATCH
D2
I01
REV & LATCH
D3
I11
REMOTE
D4
Содержание MSC-3
Страница 1: ...MSC 3 Instruction Manual INVENTIVE TECHNOLOGY DSP II...
Страница 3: ......
Страница 6: ...IM00120 iv IM00120...
Страница 14: ......
Страница 59: ...IM00120 45 IM00120 MSC 3 Instruction Manual Extended Features Option Wiring...
Страница 60: ......
Страница 157: ......