IM00120
75
IM00120
MSC-3 Instruction Manual
C033 DUAL RAMP
C033 DUAL RAMP
> DISABLED
Available Choices:
ENABLED
DISABLED
• Press
once to begin.
• Use the
▲
/
▼
buttons to enable or disable the menu lock.
• Press
to confirm the choice.
When this feature is enabled, the
C032 S TIME
parameter specifies the acceleration and deceleration
below the
C010 MIN Hz
setting. Above the
C010 MIN Hz
setting, the acceleration and deceleration
times are as per
C030 ACCEL TIME
and
C031 DECEL TIME
respectively. Note that there is no
C032 S TIME
when this feature is enabled. The following graph demonstrates this feature.
C010 MIN Hz
Speed
Time
Reference
Slope =
B03 MOTOR Hz / C032 S TIME
Slope =
B03 MOTOR Hz / C030 ACCEL TIME
Slope =
B03 MOTOR Hz / C031 DECEL TIME
C034 ESO RAMP
C034 ESO RAMP
10.0 sec
Range: 0.5…600.0 seconds
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
When the drive is operating in ESO mode it will use the
C034 ESO RAMP
setting for acceleration and
deceleration instead of the
C030 ACCEL TIME
and
C031 DECEL TIME
settings. The ESO Ramp time is
the time taken for the motor to go from zero speed up to motor rated speed (assuming minimum
C032 S
TIME
). A MSC-3 with the
B03 MOTOR Hz
set to 50 Hz and an
C034 ESO RAMP
set to 10 seconds will
take 10 seconds to go from 0Hz to 50Hz.