53 / 58
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
Manual of 11/06/2019 Rev. 1.8 “User Manual for 3000SP storage inverter”
ID09
HW_LLCB
us_OVP
Voltage on LLC line
is too high Hardware
protection trip
ID09- ID26: Internal errors of the 3000SP inverter.
Switch off the unit by disconnecting the AC and DC
switches, and wait for at least 5 minutes. Switch the
unit back on again by closing the AC and DC switches,
and check if the error is still present. If so, contact
Technical Support.
ID10
HW_Boost
_OVP
Boost voltage is too
high. Hardware
protection trip
ID11
HwBuckBo
ostOCP
BuckBoost current is
too high. Hardware
protection trip
ID12
HwBatOCP
Battery current is
too high. Hardware
protection trip
ID15
HwAcOCP
Grid current is too
high. Hardware
protection trip
ID17
HwADFaul
tIGrid
Sampling error of
the grid current
ID18
HwADFaul
tDCI
DCI sampling error
ID19
HwADFaul
tVGrid
Sampling error of
the grid voltage
ID21
MChip_Fau
lt
Microprocessor fault
ID22
HwAuxPo
werFault
Error on the
auxiliary supply
voltage
ID25
LLCBusOV
P
Voltage on LLC line
is too high.
ID26
SwBusOVP
Voltage on the
communication line
is too high. Software
protection trip
ID27
BatOCP
Battery current is
too high.
If the error occurs frequently, contact Technical
Support.
ID28
DciOCP
Current on the DCI is
too high
ID28-ID55 are internal errors of ME3000SP
Switch off the unit by disconnecting the AC and DC
switches, and wait for at least 5 minutes. Switch the
unit back on again by closing the AC and DC switches,
and check if the error is still present. If so, contact
Technical Support.
ID29
SwOCPInst
ant
Grid current is too
high.
ID30
BuckOCP
Current on the Buck
is too high
ID31
AcRmsOCP
Output current is too
high.