27 / 58
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
Manual of 11/06/2019 Rev. 1.8 “User Manual for 3000SP storage inverter”
In the case of Weco ReSU 4K4 batteries, press the POWER button for one second, making sure that
the RUN light turns on.
Figure 22 – Front view of a Weco ReSU 4K4 battery
In the case of batteries not equipped with BMS, turn ON any DC circuit breaker located between the
batteries and the storage inverter.
3)
Turn ON the AC circuit breaker located between the inverter and AC grid.
4)
At this point, the storage inverter should start up and be operational.
At the time of start-up, the 3000SP inverter requires the following parameters to be set:
1) Date and time
8)*Min. discharge voltage (V)
2) Country
9)*Max. discharge current (A)
3) Battery type
10)*Min. voltage threshold
4)*Battery capacity
11)*Discharge depth
5)*Max charge threshold (V)
12)*End-of-discharge V
6)*Max charge current (A)
13)*End-of-charge V
7)*Overvoltage threshold
Note: settings 4)* to 13)* will only be present if the DEFAULT option has been selected.
1)
Date and time
The date/time format of the System is expressed as “Year-Month-Day-Hours-Minutes-Seconds.” Change
the date and time using the “Up” and “Down” keys, press “OK” to confirm and move to the next digit.
Once the setting has been completed, the system will automatically move to the next section.
2)
Country
Set the code corresponding to the national standards (see the table below) using the “Up” and “Down”
keys, press “OK” to move to the next value and confirm. Once the setting has been completed, the system
will automatically move to the next section.