Manual of 11/06/2019 Rev. 1.8 “User Manual for 3000SP storage inverter”
4)
Set QV time
Select “4. Set QV time” and press “OK” to enter the menu for setting this parameter. The display
will show the following:
** represents the time to be set in seconds. Use the “Up” and “Down” keys to set the desired
value. Press “OK” and wait for “OK” to appear on the display.
This function is required by various standards for grid-connected inverters, and allows the
reactive power to be changed based on the grid frequency according to the requirements of the
local standards.
This option allows setting the delay time (expressed in seconds) with which the change in Q
power occurs.
5)
Enable 81.S1
Select “5. Enable 81.S1” and press “OK.” Select “1. Enable 81.S1” or “2. Disable 81.S1” if you
want to enable or disable this function. Press “OK” and wait for “OK” to appear on the display.
This function enables the restrictive frequency thresholds required in some cases by local
regulations.
12.
Working mode
Select “12. Working Mode” and press “OK to enter the interface for setting the working mode.
12. Working Mode
1.Set Auto Mode
2.Set %Charge Mode
3.Set Hourly Mode
4.Set Passive Mode
1)
Set Auto Mode
Select “1. Set Auto Mode” and press “OK” to set the automatic mode. In this mode, the device
will automatically establish the start and end of the charging to ensure that the energy stored
in the battery and the battery charge state are optimal. Below is an example of how the system
operates in automatic mode.
Set
:
** s