36 / 58
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
Manual of 11/06/2019 Rev. 1.8 “User Manual for 3000SP storage inverter”
2.
Delete Energy Data
Select “2. Delete Energy Data” and press “OK.” The display will show “Enter PWD!” Press “OK” to
enter the password “0001” using the “Up” and “Down” keys to select the number and “OK” to move
to the next digit. If the display shows “Incorrect, try again!” press the “Menu/Back” key and enter
the password again. When the correct password is entered, the menu for resetting the statistics
will open and the data relating to the energy produced and consumed will be automatically deleted
in the appropriate section of the main menu.
3.
Clear Events
Select “3. Clear Events” and press the “OK” key twice to completely clear the events recorded; this
will clear all the errors recorded in the memory of the inverter. Wait for “OK” to appear on the
display, then press the “Menu/Back” key to return to the previous menu.
4.
Set Country
Select “4. Set Country” and press “OK” to enter the menu for setting the national grid regulations.
Press “OK” and if “Setting Disabled” appears on the display, go to item “6. Enable Country Change”
to enable this function. Once the function has been enabled, repeat the steps described above and
set the code relating to the desired national regulations. Press the “OK” key and wait for “OK” to
appear display.
For more information and to know the country regulations on board the inverter, refer to the relevant
section.
5.
Select communication address
Select “5. Select Comm. Address” and press “OK” to enter the menu for selecting the
communication address. Press the “Up” and “Down” keys to change the first digit, press OK to go to
the next one, and confirm. After setting the address, press “OK.”
The communication address indicates the address with which the inverter sends its data to the
monitoring server. Address 01 is used for single inverters; if you want to extend the monitoring to
multiple 3000SP inverters, progressive communication addresses will be used.
Note: make sure that the address entered is never 00, because this setting would exclude the
possibility of communication between the inverter and Wi-Fi network.
6.
Enable Country Change
Select “6. Enable Country Change” and press “OK”. The display will show “Enter PWD!”, press “OK”
to enter the password. Enter the password “0001” using the “Up” and “Down” keys to select the
number and “OK” to move to the next one. If the display shows “Incorrect, try again!” press the
“Menu/Back” key and enter the password again.
This operation must be carried out to change the Country Code if it has not been changed during
the last 24 hours of operation.
7.
Language
Select “7. Language” and press “OK” to enter the menu for selecting the language. Select the
language using the “Up” and “Down” keys; then press “OK” to confirm.